Time-To-Live (TTL)
The TTL value (8-bit value) limits the number of routers a sent package passes on the way to
its target.
0x23A1:006 (P510.06): Time-to-live value (TTL)
The parameters for the IP sengs of the inverter are described below.
Parameter
Address Name / seng range / [default seng] Info
0x23B1:001
(P510.01)
Modbus -TCP/IP sengs: IP address
(MBTCP sengs: IP address)
0.0.0.0 ... [192.168.124.16] ... 255.255.255.255
From version 04.00
Set IP address.
The default seng 276605120 corresponds to the IP address
192.168.124.16.
276605120 = 0x107CA8C0 à 0xC0.0xA8.0x7C.0x10 = 192.168.124.16
0x23B1:002
(P510.02)
Modbus -TCP/IP sengs: Subnet
(MBTCP sengs: Subnet)
0.0.0.0 ... [255.255.255.0] ... 255.255.255.255
From version 04.00
Set subnet mask.
The default seng 16777215 corresponds to the subnet mask
255.255.255.0.
16777215 = 0xFFFFFF à 0xFF.0xFF.0xFF.0x00 = 255.255.255.0
0x23B1:003
(P510.03)
Modbus -TCP/IP sengs: Gateway
(MBTCP sengs: Gateway)
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
From version 04.00
Set gateway address.
Example
The seng 276344004 corresponds to the gateway address
196.172.120.16.
276344004 = 0x1078ACC4 à 0xC4.0xAC.0x78.0x10 = 196.172.120.16
0x23B1:005
(P510.05)
Modbus -TCP/IP sengs: IP conguraon
(MBTCP sengs: IP conguraon)
From version 04.00
Set IP conguraon.
0 Stored IP The currently saved IP conguraon is used.
1 BOOTP The IP conguraon is assigned by the master via BOOTP.
2 DHCP The IP conguraon is assigned by the Master via DHCP.
The assignment of a gateway address that is not in the same subnetwork
as the IP address, is denied.
0x23B1:006
(P510.06)
Modbus -TCP/IP sengs: Time-to-live value (TTL)
(MBTCP sengs: TTL value)
1 ... [32] ... 255
From version 04.00
Seng of the TTL value for the validity of data packages in the network.
0x23B1:011
(P510.11)
Modbus -TCP/IP sengs: Secondary port
(MBTCP sengs: Secondary port)
0 ... [502] ... 65535
From version 04.00
Set port number for a second port.
12.13.2.2 Baud rate seng
Set the baud rate for port 1 in 0x23B4:001 (P512.01) and for port 2 in 0x23B4:002
(P512.02).
The automac detecon of the baud rate is preset for the ports.
The acve baud rate is displayed for port 1 in 0x23B5:001 (P513.01) and for port 2 in
0x23B5:002 (P513.02).
Parameter
Address Name / seng range / [default seng] Info
0x23B4:001
(P512.01)
Port sengs: Port 1
(Port sengs: Port 1)
From version 04.00
Set baud rate for the port 1.
0 Auto-Negoaon
1 10 Mbps
2 100 Mbps
5 10 Mbps/Half Duplex
6 10 Mbps/Full Duplex
7 100 Mbps/Half Duplex
8 100 Mbps/Full Duplex