11.2.1.2 Example: Input range 0 ... 10 V ≡ seng range -40 ... +40 Hz
In this example, a bipolar seng range and a dead band with 2 % are congured.
Parameter Designaon Seng for this example
0x2636:001 (P430.01) Analog input 1: Input range 0 ... 10 VDC [0]
0x2636:002 (P430.02) Analog input 1: Min frequency value -40.0 Hz
0x2636:003 (P430.03) Analog input 1: Max frequency value 40.0 Hz
0x2636:006 (P430.06) Analog input 1: Filter me 10 ms
0x2636:007 (P430.07) Analog input 1: Dead band 2.0 %
10
0
100
[%]
[V]
0
100
0
40
-40
2 %
[Hz]
[%]
2 %
0
AI1
%
Hz
V
%
10 ms 2 %0 ... 10 VDC -40 ... 40 Hz
11.2.1.3 Example: Input range -10 ... +10 V ≡ seng range -40 ... +40 Hz
In this example, the input range of the analog input is bipolar. For the seng range that is
bipolar as well, a dead band with 2 % is congured.
Parameter Designaon Seng for this example
0x2636:001 (P430.01) Analog input 1: Input range -10 ... +10 VDC [3]
0x2636:002 (P430.02) Analog input 1: Min frequency value -40.0 Hz
0x2636:003 (P430.03) Analog input 1: Max frequency value 40.0 Hz
0x2636:006 (P430.06) Analog input 1: Filter me 10 ms
0x2636:007 (P430.07) Analog input 1: Dead band 2.0 %
-100
-40
10
100
[%]
[V]
100
40
2 %
[Hz]
[%]
2 %
-10
-100
AI1
%
Hz
V
%
10 ms 2 %-10 ... +10 VDC -40 ... 40 Hz
I/O extensions and control connecons
Congure analog inputs
Analog input 1
258