Address Name / seng range / [default seng] Info
0x4008:004
(P590.04)
Process input words: NetWordIN4
(NetWordINx: NetWordIN4)
0.0 ... [0.0] ... 100.0 %
Mappable data word for oponal control of an analog output via net-
work.
Assignment of the analog outputs:
Analog output 1: 0x2639:002 (P440.02) = "NetWordIN4 [21]"
Analog output 2: 0x263A:002 (P441.02) = "NetWordIN4 [21]"
Related topics
4Congure analog outputs ^ 275
12.3.1.4 Addive voltage impression via network
The mappable data word NetWordIN5 is available for the oponal specicaon of an addive
voltage setpoint via the network.
Parameter
Address Name / seng range / [default seng] Info
0x4008:005
(P590.05)
Process input words: NetWordIN5
(NetWordINx: NetWordIN5)
-100.0 ... [0.0] ... 100.0 %
Mappable data word for oponally specifying an addive voltage set-
point via network.
100 % ≡ Rated voltage 0x2C01:007 (P320.07)
This value is used if "Network [3]" is selected in 0x2B13:002.
Related topics
4Addive voltage impression ^ 190
Conguring the network
Further mappable parameters
Process input data