17.5.2 Error conguraon
The errors can be divided into two types:
•
Errors with predened error type
•
Errors with congurable error type
Especially crical errors are permanently set to the "Fault" error type in order to protect inver-
ter and motor from damages.
In case of errors with congurable error type, the default seng can be changed in considera-
on of safety aspects and the operaonal performance. The selecon "No response [0]" is,
however, only available for minor errors.
The "Error codes, causes and remedies" table lists the error type for each error. If the error
type can be congured by the user, the "adjustable in" column displays the corresponding
parameter. ^ 616
17.5.3 Error reset
If the error condion is not acve anymore, there are several opons to reset an acve error
and thus leave the error state again:
•
Via the keypad key . 4Error reset with keypad^ 553
•
Via the trigger assigned to the "Reset fault" funcon.
•
Via the buon in the »EASY Starter« ("Diagnoscs" tab).
•
In the default seng of 0x400E:008 (P505.08) via bit 7 in the mappable data word Net-
WordIN1 0x4008:001 (P590.01).
•
Via bit 7 in the mappable CiA 402 control word 0x6040.
•
Via bit 2 in the mappable AC Drive control word 0x400B:001 (P592.01).
•
Via bit 11 in the mappable LECOM control word 0x400B:002 (P592.02).
Notes:
•
Certain errors can only be reset by mains switching.
•
Certain errors (e. g. earth fault or short circuit of the motor phases) may cause a blocking
me. In this case, the error can be reset only aer the blocking me has elapsed. An acve
blocking me is displayed via bit 14 in the inverter status word 0x2831.
The "Error codes, causes and remedies" table gives the blocking me (if available) for each
error. This table also shows whether mains switching is required for the error reset. ^ 616
Parameter
Address Name / seng range / [default seng] Info
0x2631:004
(P400.04)
Funcon list: Reset fault
(Funcon list: Reset fault)
•
Further seng opons: 4Trigger list ^ 64
Assignment of a trigger for the "Reset fault" funcon.
Trigger = FALSE↗TRUE (edge): The acve error is reset (acknowledged) if
the error condion no longer exists and the error is reseable.
Trigger = FALSE: no acon.
12 Digital input 2 State of X3/DI2, taking an inversion set in 0x2632:002 (P411.02) into
consideraon.
Diagnoscs and fault eliminaon
Error handling
Error conguraon
613