Address Name / seng range / [default seng] Info
0x2839:006 Fault conguraon: Fault handling in case of state
change
Selecon whether a pending error is to be reset via the funcons "Ena-
ble inverter" 0x2631:001 (P400.01) and "Run" 0x2631:002 (P400.02) as
well.
0 Reset fault
1 Do not reset fault
Example for operang mode
•
Switch S1 starts the motor in forward direcon of rotaon. Switch S1 in the inial posion
stops the motor again.
•
Switch S2 resets the current error if the error condion is not acve anymore and the error
is reseable.
•
The switches/sensors S3 and S4 serve to set the inverter from the process to the error sta-
tus. 4User-dened error triggering^ 513
Connecon plan Funcon
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
DO1
X3
S1 S2 S3 S4
1k ...10k
0 ... 10 V
R1
Potenometer R1 Frequency setpoint selecon
Switch S1 Run
Switch S2 Reset fault
Switch S3 Acvate fault 1
Switch S4 Acvate fault 2
Parameter Designaon Seng for this example
0x2631:001 (P400.01) Enable inverter Constant TRUE [1]
0x2631:002 (P400.02) Run Digital input 1 [11]
0x2631:004 (P400.04) Reset fault Digital input 2 [12]
0x2631:013 (P400.13) Reverse rotaonal direcon Not connected [0]
0x2631:018 (P400.18) Acvate preset (bit 0) Not connected [0]
0x2631:043 (P400.43) Acvate fault 1 Digital input 3 [13]
0x2631:044 (P400.44) Acvate fault 2 Digital input 4 [14]
0x2824 (P200.00) Control selecon Flexible I/O conguraon [0]
0x2838:003 (P203.03) Stop method Standard ramp [1]
0x2860:001 (P201.01) Frequency control: Default setpoint source Analog input 1 [2]
0x2918 (P221.00) Deceleraon me 1 5.0 s
0x291C (P225.00) Quick stop deceleraon me 1.0 s
Diagnoscs and fault eliminaon
Error handling
Error reset
614