7.4.2 Example: Change-over from AI1 setpoint to keypad setpoint
•
The analog input 1 is set as standard setpoint source.
•
Switch S1 starts the motor in forward direcon of rotaon. Switch S1 in the inial posion
stops the motor again.
•
Switch S2 switches the direcon of rotaon.
•
Switch S3 acvates the keypad as setpoint source. The keypad setpoint can be changed in
the operang mode via the navigaon keys and keypad key.
Connecon plan Funcon
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
DO1
X3
S1 S2 S3
1k ...10k
0 ... 10 V
R1
Potenometer R1 Frequency setpoint selecon
Switch S1 Run
Switch S2 Reverse rotaonal direcon
Switch S3 Acvate keypad setpoint
Parameter Designaon Seng for this example
0x2601:001 (P202.01) Keypad setpoints: Frequency setpoint 20.0 Hz
0x2631:001 (P400.01) Enable inverter Constant TRUE [1]
0x2631:002 (P400.02) Run Digital input 1 [11]
0x2631:004 (P400.04) Reset fault Not connected [0]
0x2631:013 (P400.13) Reverse rotaonal direcon Digital input 2 [12]
0x2631:016 (P400.16) Acvate keypad setpoint Digital input 3 [13]
0x2824 (P200.00) Control selecon Flexible I/O conguraon [0]
0x2838:003 (P203.03) Stop method Standard ramp [1]
0x2860:001 (P201.01) Frequency control: Default setpoint source Analog input 1 [2]
Conguring the frequency control
Changing the setpoint source during operaon
Example: Change-over from AI1 setpoint to keypad setpoint
136