12.6.5.3 Enable operaon
This command enables the operaon and stop an acve quick stop again.
A changeover to the "Operaon enabled" device status takes place.
The output stages of the inverter become acve.
A From all states
B Power secon inhibited (pulse inhibit)
C Power secon enabled
Bit paern in the CiA 402 control word (0x6040)
Bit 15 ... 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reserved
(specic)
Reset fault Operang mode dependent Operaon
enabled
Acvang
quick stop
Establish read-
iness for oper-
aon
Switch-on
X 0 X X X 1 1 1 1
X = state is not relevant
If the device status "Operaon enabled" is signalled in the CiA 402 status word, the inverter is
ready to accept set points from the network master.
Conguring the network
Device prole CiA 402
Commands for device state control
313