12.11.5 Monitoring
The parameters for seng network monitoring funcons are described below.
Parameter
Address Name / seng range / [default seng] Info
0x23A1:010
(P510.10)
EtherNet/IP sengs: Timeout
(EtherN/IP se.: Timeout)
500 ... [10000] ... 65535 ms
From version 02.00
Seng of the maximum permissible me-out for the CIP communica-
on.
When the specied monitoring me has elapsed, the response set in
0x2859:007 (P515.07) is triggered in the inverter.
0x2859:001
(P515.01)
EtherNet/IP monitoring: Watchdog elapsed
(EtherN/IP monit.: WD elapsed)
From version 02.00
Selecon of the response to a permanent interrupon of the communi-
caon to the Scanner, e. g. by cable break or failure of the Scanner.
Associated error code:
33168 | 0x8190 - Network: watchdog meout
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
0x2859:003
(P515.03)
EtherNet/IP monitoring: Invalid conguraon
(EtherN/IP monit.: Invalid cong)
From version 02.00
Selecon of the response triggered by the recepon of invalid congura-
on data.
Associated error code:
33414 | 0x8286 - Network: PDO mapping error
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
0x2859:004
(P515.04)
EtherNet/IP monitoring: Inialisaon error
(EtherN/IP monit.: Init. error)
From version 02.00
Selecon of the response triggered by the occurrence of an error during
the inialisaon of the network component.
Associated error code:
33170 | 0x8192 - Network: inialisaon error
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
0x2859:005
(P515.05)
EtherNet/IP monitoring: Invalid process data
(EtherN/IP monit.: Inval. proc.data)
From version 02.00
Selecon of the response triggered by the recepon of invalid process
data.
Associated error code:
33171 | 0x8193 - Network: invalid cyclic process data
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
0x2859:006
(P515.06)
EtherNet/IP monitoring: Timeout explicit message
(EtherN/IP monit.: Timeout ExplMsg)
From version 02.00
Selecon of the response to me-outs during the transfer of Explicit
Messages.
Associated error code:
33042 | 0x8112 - Network: meout explicit message
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
0x2859:007
(P515.07)
EtherNet/IP monitoring: Timeout communicaon
(EtherN/IP monit.: Timeout Comm.)
From version 02.00
Selecon of the response to the me-out during the CIP communicaon.
Selecon of the response to the me-out during the CIP communicaon.
The monitoring me for the CIP communicaon is dened in
0x23A1:010 (P510.10).
Associated error code:
33044 | 0x8114 - Network: overall communicaon meout
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault