7 Conguring the frequency control
7.1 Basic seng
In the following, the steps required for conguring the frequency control are described.
1.
Set the operang mode "MS: Velocity mode [-2]" (default seng) in 0x6060 (P301.00).
2.
Select the standard setpoint source for the frequency control in 0x2860:001 (P201.01).
3.
Congure the selected standard setpoint source. 4Congure setpoint sources ^ 86
4.
Adjust the ramp
mes to the applicaon. 4Ramp mes ^ 84
5.
Oponal: Conguring the process controller ^ 116
The following signal ow shows the internal setpoint logics:
0
1
0x2B0E
0x4020:002
0x4020:001
0x2631:045
0x4020:004
0x401F:001
0x401F:002
1...4
0
0x6060
Hz
PID Unit
PID Unit
Hz
0x2860:001
0x2860:002
MS = manufacturer specific
[Hz]
Frequency setpoint
PID setpoint
PID variable
Speed feedforward control
Motor control
Modes of operation
MS: Velocity mode [-2]
(default setting)
Deactivate
PID control
(trigger)
Process controller: operating mode
The frequency control is now acve and the inverter responds to the frequency setpoint given
by the selected setpoint source.
7.1.1 Standard setpoint source
The selected "setpoint source" serves to provide the inverter with its setpoint. The setpoint
source can be selected individually for each operang mode.
Possible setpoint sources:
Analog inputs
Keypad
Network
Parameterisable setpoints (presets)
Digital inputs (congured as HTL input for pulse train or HTL encoder)
"Motor potenometer" funcon
"Sequencer" funcon
Details
For applicaons only requiring one setpoint, it is sucient to dene the standard setpoint
source in 0x2860:001 (P201.01).
For applicaons requiring a change-over of the setpoint source during operaon, the func-
ons for setpoint change-over have to be congured accordingly. 4Changing the setpoint
source during operaon ^ 130
Parameter
Address Name / seng range / [default seng] Info
0x2860:001
(P201.01)
Frequency control: Default setpoint source
(Freq. setp. src.)
Selecon of the standard setpoint source for operang mode "MS:
Velocity mode".
The selected standard setpoint source is always acve in the operat-
ing mode 0x6060 (P301.00) = "MS: Velocity mode [-2]" when no set-
point change-over to another setpoint source via corresponding trig-
gers/funcons is acve.
4Changing the setpoint source during operaon^ 130
1 Keypad The setpoint is specied locally by the keypad.
Default seng: 0x2601:001 (P202.01)
Use the and navigaon keys to change the keypad setpoint
(also during running operaon).
Conguring the frequency control
82