7 Conguring the frequency control
7.1 Basic seng
In the following, the steps required for conguring the frequency control are described.
1.
Set the operang mode "MS: Velocity mode [-2]" (default seng) in 0x6060 (P301.00).
2.
Select the standard setpoint source for the frequency control in 0x2860:001 (P201.01).
3.
Congure the selected standard setpoint source. 4Congure setpoint sources ^ 86
4.
Adjust the ramp
mes to the applicaon. 4Ramp mes ^ 84
5.
Oponal: Conguring the process controller ^ 116
The following signal ow shows the internal setpoint logics:
0
1
0x2B0E
0x4020:002
0x4020:001
0x2631:045
0x4020:004
0x401F:001
0x401F:002
1...4
0
0x6060
Hz
PID Unit
PID Unit
Hz
0x2860:001
0x2860:002
MS = manufacturer specific
[Hz]
Frequency setpoint
PID setpoint
PID variable
Speed feedforward control
Motor control
Modes of operation
MS: Velocity mode [-2]
(default setting)
Deactivate
PID control
(trigger)
Process controller: operating mode
The frequency control is now acve and the inverter responds to the frequency setpoint given
by the selected setpoint source.
7.1.1 Standard setpoint source
The selected "setpoint source" serves to provide the inverter with its setpoint. The setpoint
source can be selected individually for each operang mode.
Possible setpoint sources:
•
Analog inputs
•
Keypad
•
Network
•
Parameterisable setpoints (presets)
•
Digital inputs (congured as HTL input for pulse train or HTL encoder)
•
"Motor potenometer" funcon
•
"Sequencer" funcon
Details
•
For applicaons only requiring one setpoint, it is sucient to dene the standard setpoint
source in 0x2860:001 (P201.01).
•
For applicaons requiring a change-over of the setpoint source during operaon, the func-
ons for setpoint change-over have to be congured accordingly. 4Changing the setpoint
source during operaon ^ 130
Parameter
Address Name / seng range / [default seng] Info
0x2860:001
(P201.01)
Frequency control: Default setpoint source
(Freq. setp. src.)
Selecon of the standard setpoint source for operang mode "MS:
Velocity mode".
•
The selected standard setpoint source is always acve in the operat-
ing mode 0x6060 (P301.00) = "MS: Velocity mode [-2]" when no set-
point change-over to another setpoint source via corresponding trig-
gers/funcons is acve.
4Changing the setpoint source during operaon^ 130
1 Keypad The setpoint is specied locally by the keypad.
•
Default seng: 0x2601:001 (P202.01)
•
Use the and navigaon keys to change the keypad setpoint
(also during running operaon).
Conguring the frequency control