17.5.1.1 Timeout for error response
If an error occurs that does not immediately cause a switch-o, the "Fault reacon acve"
device status inially becomes acve. The motor is brought to a standsll with quick stop
ramp. The change to the device status "Fault" is only made aer the quick stop (motor at
standsll) has been executed or aer an adjustable meout me has expired.
Details
In the device status "Fault reacon acve"
•
only the parameters of the inverter can be changed that do not require an inverter disable.
•
a holding brake in brake mode 0x2820:001 (P712.01) = "Automacally (via device state)
[0]" is triggered for closing.
•
the motor control connues to be operable.
Ready to
switch on
Not ready to
switch on
Switched
on
Operation
enabled
Fault reaction
active
Fault
active
Switch on
disabled
Quick stop
active
Power on
①
From all states
②
Power secon inhibited (pulse inhibit)
③
Power secon enabled
Diagnosc parameters:
•
0x282A:005 (P126.05) displays the current device status of the inverter
Parameter
Address Name / seng range / [default seng] Info
0x2826 Time-out for error response
0.0 ... [6.0] ... 100.0 s
This mer is started when a change-over to the "Fault reacon acve"
device status takes place. If the motor is sll rotang aer the me-out
me has elapsed, a change-over to the "Fault" device status takes place.
•
In case of a serious error, an immediate change-over to the "Fault"
device status takes place.
CAUTION!
Changing this parameter may cause a longer rampme in the event of an
error. This must be considered when changing this parameter.
Related topics
4Automac restart aer a fault^ 512
Diagnoscs and fault eliminaon
Error handling