18.1.3 EMC data
Operaon on public supply systems
Take measures to limit the expected radio inter-
ference:
The machine or system manufacturer is responsible for compli-
ance with the requirements for the machine/system!
< 1 kW: With mains choke
EN 61000-3-2
> 1 kW for mains current ≤ 16 A: Without addi-
onal measures
Mains current > 16 A: with mains choke or
mains lter, when dimensioned for rated
power.
EN 61000-3-12
Noise emission
Category C1 EN 61800-3 See rated data
Category C2 EN 61800-3 See rated data
Category C3 EN 61800-3 See rated data
Noise immunity
Fullls requirements according to EN 61800-3
18.1.4 Motor connecon
Requirements for the shielded motor cable
Capacitance per unit length
C-core-core/C-core-shielding < 75/150 pF/m
≤ 2.5 mm² / AWG 14
C-core-core/C-core-shielding < 150/300 pF/m ≥ 4 mm² / AWG 12
Electric strength
Uo/U = 0.6/1.0 kV
Uo = r.m.s. value external conductor to PE
U = r.m.s. value from external conductor to external conductor
U ≥ 600 V UL U = r.m.s. value from external conductor to external conductor
18.1.5 Environmental condions
Energy eciency
Class IE2 EN 50598-2
Climate
1K3 (-25 ... +60°C) EN 60721-3-1 Storage
2K3 (-25 ... +70°C) EN 60721-3-2 Transport
3K3 (-10 ... +55°C) EN 60721-3-3 Operaon
Operaon at a switching frequency of 2 or 4 kHz: above +45°C:
reduce rated output current by 2.5 %/°C
Operaon at a switching frequency of 8 or 16 kHz: above +40°C:
reduce rated output current by 2.5 %/°C
Site altude
0 … 1000 m amsl
1000 … 4000 m amsl Reduce rated output current by 5 %/1000 m
Polluon
Degree of polluon 2
EN 61800-5-1
UL 61800-5-1
Vibraon resistance
Transport
2M2 (sine, shock) EN 60721-3-2
In original packaging
up to 45 kW
Operaon
Amplitude 1 mm
Germanischer Lloyd
5 ... 13.2 Hz
Acceleraon resistant up to 0.7 g 13.2 ... 100 Hz
Up to 11 kW
Amplitude 0.075 mm
EN 61800-5-1
10 ... 57 Hz
Acceleraon resistant up to 1 g 57 ... 150 Hz
Technical data
Standards and operang condions
Environmental condions
638