Loading...
Address Name / seng range / [default seng] Info
0x1F9E NMT_ResetCmd_U8
Read only
From version 05.00
This object enables the managing node to execute a reset command in
the controlled node.
Note!
A reset command at a single POWERLINK node in the network can cause
cycle and monitoring errors.
0x23C1:004 POWERLINK sengs: Node ID
0 ... [0] ... 239
From version 05.00
Seng of the unique node address (node ID) in the network.
The node address set here is only eecve if both rotary encoder
switches are set to "0".
In the default seng "0", the rotary encoder switch seng is used.
The resulng IP address is "192.168.100.[node address]".
A changed node address only becomes eecve aer a restart of the
device.
12.14.3 Process data transfer
POWERLINK transfers process data, parameter data, conguraon data and diagnosc data
between the managing node and the involved controlled nodes in the network. Depending on
their me-crical behaviour, the data is transmied via corresponding communicaon chan-
nels.
Details
Process data is transmied cyclically between the managing node and the controlled node
(permanent exchange of current input and output data).
The transfer of process data is me-crical.
The process data serves to control the POWERLINK nodes.
The process data can be directly accessed by the managing node. The data in the PLC, for
instance, are directly stored in the I/O area.
The contents of the process data are dened via I/O data mapping.
Process data is not saved in the device.
Process data (RxPDO):
0x4008:001 (P590.01) (NetWordIN1)
0x400B:013 (P592.13) (Network frequency setpoint [+/-16384])
Process data (TxPDO):
0x400A:001 (P591.01) (NetWordOUT1)
0x400C:009 (P593.09) (Frequency [+/-16384])
0x2D88 (P104.00) (Motor current)
0x4050:002 (internal parameters)
Parameter
Address Name / seng range / [default seng] Info
0x1400:001 PDO_RxCommParam_00h_REC: NodeID_U8
0 ... [0] ... 255
From version 05.00
Seng of the node ID for RPDO1.
0x1400:002 PDO_RxCommParam_00h_REC: MappingVersion_U8
Read only
From version 05.00
Display of the version of the RPDO1 mapping.
0x1600:001 ...
0x1600:016
PDO_RxMappParam_00h_REC: ObjectMapping_U64
1 ... ObjectMapping_U64 16
0 ... [0] ... 18446744073709551615
Mapping entries 1 ... 16 for RPDO1.
0x1800:001 PDO_TxCommParam_00h_REC: NodeID_U8
Read only
From version 05.00
Display of the node ID of the TPDO1 receiver.
0x1800:002 PDO_TxCommParam_00h_REC: MappingVersion_U8
Read only
From version 05.00
Display of the TPDO1 mapping version.
0x1A00:001 ...
0x1A00:016
PDO_TxMappParam_00h_REC: ObjectMapping_U64
1 ... ObjectMapping_U64 16
0 ... [0] ... 18446744073709551615
Mapping entries 1 ... 16 for TPDO1.
Conguring the network