Address Name / seng range / [default seng] Info
201 Internal value (from version 05.00) Internal values of the manufacturer.
202 Internal value (from version 05.00)
203 Internal value (from version 05.00)
204 Internal value (from version 05.00)
205 Internal value (from version 05.00)
206 Internal value (from version 05.00)
0x2631:011
(P400.11)
Funcon list: Jog reverse (CCW)
(Funcon list: Jog reverse)
•
Seng can only be changed if the inverter is inhibi-
ted.
•
Further seng opons: 4Trigger list ^ 64
Assignment of a trigger for the "Jog reverse (CCW)" funcon.
Trigger = TRUE: Let motor rotate backward with preset 6.
Trigger = FALSE: Stop motor.
CAUTION!
The jog operaon has a higher priority than the "Run" funcon, all other
start commands and the keypad key .
•
If jog operaon is acve, the motor cannot be stopped with the previ-
ously menoned funcons!
•
However, jog operaon can be interrupted by the "Quick stop" func-
on.
Notes:
•
The preset 6 can be set in 0x2911:006 (P450.06).
•
The stop method can be selected in 0x2838:003 (P203.03).
•
If "Jog foward (CW)" and "Jog reverse (CCW)" are acvated at the
same me, the motor is stopped using the set stop method and jog
operaon must be triggered again.
•
Jog operaon cannot be started automacally. The "Start at power-
up" opon in 0x2838:002 (P203.02) does not apply to jog operaon.
4Example: Jog forward/Jog reverse^ 74
0 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:013
(P400.13)
Funcon list: Reverse rotaonal direcon
(Funcon list: Reverse rot.dir.)
•
Seng can only be changed if the inverter is inhibi-
ted.
•
Further seng opons: 4Trigger list ^ 64
Assignment of a trigger for the "Reverse rotaonal direcon" funcon.
Trigger = TRUE: the setpoint specied is inverted (i. e. the sign is inver-
ted).
Trigger = FALSE: no acon / deacvate funcon again.
4Example: Start/stop (1 signal) and reversal^ 67
13 Digital input 3 State of X3/DI3, taking an inversion set in 0x2632:003 (P411.03) into
consideraon.
6.2.1 Trigger list
The trigger list lists all selecon opons (triggers) for the funcons which can be congured
using the parameters 0x2631:xx (P400.xx).
Selecon Info
0 Not connected No trigger assigned (trigger is constantly FALSE).
1 Constant TRUE Trigger is constantly TRUE.
11 Digital input 1 State of X3/DI1, taking an inversion set in 0x2632:001 (P411.01) into
consideraon.
12 Digital input 2 State of X3/DI2, taking an inversion set in 0x2632:002 (P411.02) into
consideraon.
13 Digital input 3 State of X3/DI3, taking an inversion set in 0x2632:003 (P411.03) into
consideraon.
14 Digital input 4 State of X3/DI4, taking an inversion set in 0x2632:004 (P411.04) into
consideraon.
15 Digital input 5 State of X3/DI5, taking an inversion set in 0x2632:005 (P411.05) into
consideraon.
16 Digital input 6 State of X3/DI6, taking an inversion set in 0x2632:006 (P411.06) into
consideraon.
Digital input 6 is only available in the Control Unit (CU) with applicaon
I/O.
17 Digital input 7 State of X3/DI7, taking an inversion set in 0x2632:007 (P411.07) into
consideraon.
Digital input 7 is only available in the Control Unit (CU) with applicaon
I/O.
Start, stop and rotang direcon commands
Flexible I/O conguraon of the start, stop and rotang direcon commands
Trigger list