Address Name / seng range / [default seng] Info
201 Internal value (from version 05.00) Internal values of the manufacturer.
202 Internal value (from version 05.00)
203 Internal value (from version 05.00)
204 Internal value (from version 05.00)
205 Internal value (from version 05.00)
206 Internal value (from version 05.00)
0x2631:011
(P400.11)
Funcon list: Jog reverse (CCW)
(Funcon list: Jog reverse)
Seng can only be changed if the inverter is inhibi-
ted.
Further seng opons: 4Trigger list ^ 64
Assignment of a trigger for the "Jog reverse (CCW)" funcon.
Trigger = TRUE: Let motor rotate backward with preset 6.
Trigger = FALSE: Stop motor.
CAUTION!
The jog operaon has a higher priority than the "Run" funcon, all other
start commands and the keypad key .
If jog operaon is acve, the motor cannot be stopped with the previ-
ously menoned funcons!
However, jog operaon can be interrupted by the "Quick stop" func-
on.
Notes:
The preset 6 can be set in 0x2911:006 (P450.06).
The stop method can be selected in 0x2838:003 (P203.03).
If "Jog foward (CW)" and "Jog reverse (CCW)" are acvated at the
same me, the motor is stopped using the set stop method and jog
operaon must be triggered again.
Jog operaon cannot be started automacally. The "Start at power-
up" opon in 0x2838:002 (P203.02) does not apply to jog operaon.
4Example: Jog forward/Jog reverse^ 74
0 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:013
(P400.13)
Funcon list: Reverse rotaonal direcon
(Funcon list: Reverse rot.dir.)
Seng can only be changed if the inverter is inhibi-
ted.
Further seng opons: 4Trigger list ^ 64
Assignment of a trigger for the "Reverse rotaonal direcon" funcon.
Trigger = TRUE: the setpoint specied is inverted (i. e. the sign is inver-
ted).
Trigger = FALSE: no acon / deacvate funcon again.
4Example: Start/stop (1 signal) and reversal^ 67
13 Digital input 3 State of X3/DI3, taking an inversion set in 0x2632:003 (P411.03) into
consideraon.
6.2.1 Trigger list
The trigger list lists all selecon opons (triggers) for the funcons which can be congured
using the parameters 0x2631:xx (P400.xx).
Selecon Info
0 Not connected No trigger assigned (trigger is constantly FALSE).
1 Constant TRUE Trigger is constantly TRUE.
11 Digital input 1 State of X3/DI1, taking an inversion set in 0x2632:001 (P411.01) into
consideraon.
12 Digital input 2 State of X3/DI2, taking an inversion set in 0x2632:002 (P411.02) into
consideraon.
13 Digital input 3 State of X3/DI3, taking an inversion set in 0x2632:003 (P411.03) into
consideraon.
14 Digital input 4 State of X3/DI4, taking an inversion set in 0x2632:004 (P411.04) into
consideraon.
15 Digital input 5 State of X3/DI5, taking an inversion set in 0x2632:005 (P411.05) into
consideraon.
16 Digital input 6 State of X3/DI6, taking an inversion set in 0x2632:006 (P411.06) into
consideraon.
Digital input 6 is only available in the Control Unit (CU) with applicaon
I/O.
17 Digital input 7 State of X3/DI7, taking an inversion set in 0x2632:007 (P411.07) into
consideraon.
Digital input 7 is only available in the Control Unit (CU) with applicaon
I/O.
Start, stop and rotang direcon commands
Flexible I/O conguraon of the start, stop and rotang direcon commands
Trigger list
64