Selecon Info
50 Running TRUE if inverter and start are enabled and output frequency > 0.2 Hz.
Otherwise FALSE.
51 Ready for operaon TRUE if inverter is ready for operaon (no error acve, no STO acve and
DC-bus voltage ok). Otherwise FALSE.
53 Stop acve TRUE if inverter is enabled and motor is not started and output fre-
quency = 0.
54 Quick stop acve TRUE if quick stop is acve. Otherwise FALSE.
58 Device warning acve TRUE if warning is acve. Otherwise FALSE.
•
A warning has no impact on the operang status of the inverter.
•
A warning is reset automacally if the cause has been eliminated.
59 Device trouble acve TRUE if a fault is acve. Otherwise FALSE.
•
In the event of a fault, the motor is brought to a standsll with the
quick stop ramp. The inverter is then disabled.
•
Excepon: In case of a serious fault, the inverter is disabled immedi-
ately. The motor becomes torqueless (coasts).
•
The error state will be le automacally if the error condion is not
acve anymore.
•
The restart behaviour aer trouble can be congured. 4Automac
restart aer a fault^ 512
60 Heatsink temperature warning acve TRUE if current heatsink temperature > warning threshold for tempera-
ture monitoring. Otherwise FALSE.
•
Display of the current heatsink temperature in 0x2D84:001 (P117.01).
•
Seng of the warning threshold in 0x2D84:002.
68 Stop command acve TRUE if delay to standsll acve. Otherwise FALSE.
69 Rotaonal direcon reversed TRUE if output frequency is negave. Otherwise FALSE.
70 Frequency threshold exceeded TRUE if current output frequency > frequency threshold. Otherwise
FALSE.
•
Display of the current output frequency in 0x2DDD (P100.00).
•
Seng Frequency threshold in 0x4005 (P412.00).
4Trigger acon if a frequency threshold is exceeded^ 536
71 Actual speed = 0
TRUE if current output frequency = 0 Hz (± 0.01 Hz), irrespecve of the
operang mode. Otherwise FALSE.
•
Display of the current output frequency in 0x2DDD (P100.00).
78 Current limit reached
TRUE if current motor current ≥ maximum current. Otherwise FALSE.
•
Display of the present motor current in 0x2D88 (P104.00).
•
Seng for the maximum current in 0x6073 (P324.00).
79 Torque limit reached (from version 02.00) TRUE if torque limit has been reached or exceeded. Otherwise FALSE.
•
Seng "Actual posive torque limit" in 0x2949:003 (P337.03).
•
Seng Actual negave torque limit in 0x2949:004 (P337.04).
Motor torque monitoring ^ 238
81 Error of analog input 1 acve TRUE if the monitoring of the input signal at the analog input 1 has
responded. Otherwise FALSE.
This trigger is set as a funcon of the following sengs:
•
Monitoring threshold0x2636:008 (P430.08)
•
Monitoring condion0x2636:009 (P430.09)
The seng of the Error response in 0x2636:010 (P430.10) has no eect
on this trigger.
4Analog input 1^ 255
82 Error of analog input 2 acve TRUE if the monitoring of the input signal at the analog input 2 has
responded. Otherwise FALSE.
This trigger is set as a funcon of the following sengs:
•
Monitoring threshold0x2637:008 (P431.08)
•
Monitoring condion0x2637:009 (P431.09)
The seng of the Error response in 0x2637:010 (P431.10) has no eect
on this trigger.
4Analog input 2^ 260
83 Load loss detected TRUE if actual motor current < threshold for load loss detecon aer
delay me of the load loss detecon has elapsed. Otherwise FALSE.
•
Display of the present motor current in 0x6078 (P103.00).
•
Seng Threshold in 0x4006:001 (P710.01).
•
Seng Delay me in 0x4006:002 (P710.02).
4Load loss detecon^ 212
Start, stop and rotang direcon commands
Flexible I/O conguraon of the start, stop and rotang direcon commands
Trigger list