Conguraon examples
Detailed conguraon examples can be found in the following subchapters:
4Example: Input range 0 ... 10 V ≡ seng range 0 ... 50 Hz ^ 257
4Example: Input range 0 ... 10 V ≡ seng range -40 ... +40 Hz ^ 258
4Example: Input range -10 ... +10 V ≡ seng range -40 ... +40 Hz ^ 258
4Example: Error detecon ^ 259
Parameter
Address Name / seng range / [default seng] Info
0x2636:001
(P430.01)
Analog input 1: Input range
(Analog input 1: AI1 input range)
Denion of the input range.
0 0 ... 10 VDC
1 0 ... 5 VDC
2 2 ... 10 VDC
3 -10 ... +10 VDC
4 4 ... 20 mA
5 0 ... 20 mA
0x2636:002
(P430.02)
Analog input 1: Min frequency value
(Analog input 1: AI1 freq @ min)
-1000.0 ... [0.0] ... 1000.0 Hz
Denion of the seng range for operang mode "MS: Velocity mode".
Direcon of rotaon according to sign.
The standard setpoint source for operang mode 0x6060 (P301.00) =
"MS: Velocity mode [-2]" is selected in 0x2860:001 (P201.01).
4Conguring the frequency control ^ 82
0x2636:003
(P430.03)
Analog input 1: Max frequency value
(Analog input 1: AI1 freq @ max)
Device for 50-Hz mains: -1000.0 ... [50.0] ... 1000.0 Hz
Device for 60-Hz mains: -1000.0 ... [60.0] ... 1000.0 Hz
0x2636:004
(P430.04)
Analog input 1: Min PID value
(Analog input 1: AI1 PID @ min)
-300.00 ... [0.00] ... 300.00 PID unit
Denion of the seng range for PID control.
The standard setpoint source for the reference value of PID control is
selected in 0x2860:002 (P201.02).
4Conguring the process controller ^ 116
0x2636:005
(P430.05)
Analog input 1: Max PID value
(Analog input 1: AI1 PID @ max)
-300.00 ... [100.00] ... 300.00 PID unit
0x2636:006
(P430.06)
Analog input 1: Filter me
(Analog input 1: AI1 lter me)
0 ... [10] ... 10000 ms
PT1 me constant for low-pass lter.
By the use of a low-pass lter, the impacts of noise to an analog signal
can be minimised.
For an opmum lter eect, rst the noise frequency has to be deter-
mined. The me constant then has to be set so that it equals the
reciprocal value of the double frequency.
0x2636:007
(P430.07)
Analog input 1: Dead band
(Analog input 1: AI1 dead band)
0.0 ... [0.0] ... 100.0 %
Oponal seng of a dead band that is placed symmetrically around the
frequency zero point.
If the analog input value is within the dead band, the output value for
the motor control is set to "0".
100 % ≡ maximum value of analog input (0x2636:003 (P430.03),
0x2636:005 (P430.05), 0x2636:012 (P430.12))
Example: Dead band 10% of 50Hz: -10V … 10V dead band -5Hz … 5 Hz,
0 … 10V dead band 0Hz … 5 Hz
0x2636:008
(P430.08)
Analog input 1: Monitoring threshold
(Analog input 1: AI1 monit.level)
-100.0 ... [0.0] ... 100.0 %
Monitoring threshold for analog input 1.
100 % ≡ 10 V (with conguraon as voltage input)
100 % ≡ 20 mA (with conguraon as current loop)
Excepon: in the case of a congured input range 4...20mA (0x2636:001
[4]), the monitoring is triggered at 2mA with a monitoring threshold of
0.0%.
0x2636:009
(P430.09)
Analog input 1: Monitoring condion
(Analog input 1: Monitoring cond.)
Monitoring condion for analog input 1.
If the selected condion is met, the "Error of analog input 1 acve
[81]" trigger is set to TRUE. The trigger can be assigned to a funcon
or a digital output.
If the selected condion is met for at least 500 ms, the error response
set in 0x2636:010 (P430.10) takes place.
0 Input value < trigger threshold
1 Input value > trigger threshold
I/O extensions and control connecons
Congure analog inputs
Analog input 1
256