Parameter
Address Name / seng range / [default seng] Info
0x2860:002
(P201.02)
PID control: Default setpoint source
(PID setp. src.)
Selecon of the standard setpoint source for the reference value of the
PID control.
The selected standard setpoint source is always acve with an acva-
ted PID control when no setpoint change-over to another setpoint
source via corresponding triggers/funcons is acve.
1 Keypad The setpoint is specied locally by the keypad.
Default seng: 0x2601:002 (P202.02)
Use the and navigaon keys to change the keypad setpoint
(also during running operaon).
2 Analog input 1 The setpoint is dened as analog signal via the analog input 1.
4Analog input 1^ 255
3 Analog input 2 The setpoint is dened as analog signal via the analog input 2.
4Analog input 2^ 260
4 HTL input (from version 04.00) The digital inputs DI3 and DI4 can be congured as HTL input to use an
HTL encoder as setpoint encoder or dene the setpoint as a reference
frequency ("pulse train").
4HTL encoder^ 162
4Congure digital inputs DI3/DI4 for detecng a pulse train^ 247
5 Network The setpoint is dened as process data object via the network.
4Dene setpoint via network ^ 296
11 PID preset 1 For the setpoint selecon, preset values can be parameterised and selec-
ted.
4Setpoint presets^ 87
12 PID preset 2
13 PID preset 3
14 PID preset 4
15 PID preset 5
16 PID preset 6
17 PID preset 7
18 PID preset 8
31 Segment preset 1 (from version 03.00) For the setpoint selecon, the segment presets parameterised for the
"sequencer" funcon can be selected as well.
4Sequencer ^ 91
32 Segment preset 2 (from version 03.00)
33 Segment preset 3 (from version 03.00)
34 Segment preset 4 (from version 03.00)
35 Segment preset 5 (from version 03.00)
36 Segment preset 6 (from version 03.00)
37 Segment preset 7 (from version 03.00)
38 Segment preset 8 (from version 03.00)
50 Motor potenometer The setpoint is generated by the "motor potenometer" funcon. This
funcon can be used as an alternave setpoint control which is control-
led via two signals: "MOP setpoint up" and "MOP setpoint down".
4Motor potenometer (MOP) ^ 89
201 Internal value (from version 05.00) Internal values of the manufacturer.
202 Internal value (from version 05.00)
203 Internal value (from version 05.00)
204 Internal value (from version 05.00)
205 Internal value (from version 05.00)
206 Internal value (from version 05.00)
Conguring the frequency control
Conguring the process controller
Basic seng
120