6.2 Flexible I/O conguraon of the start, stop and rotang direcon commands
Conguraon of the triggers for the basic funcons for controlling the motor.
Details
The following table contains a short overview of the basic funcons. For more details see the
following parameter descripons.
Funcon Info
Enable inverter
0x2631:001 (P400.01)
Enable/disable operaon.
•
The funcon must be set to TRUE to start the motor. Either via a digital input or the default seng "Con-
stant TRUE [1]".
•
If the funcon is set to FALSE, the inverter is disabled. The motor becomes torqueless (coasts).
4Example: Enable inverter ^ 73
Run
0x2631:002 (P400.02)
Funcon 1: Start / stop motor (default seng)
•
Funcon 1 is acve if no further start commands (start forward/start reverse) have been connected to trig-
gers, no keypad control is acve and no network control is acve.
TRUE: Let motor rotate forward (CW).
FALSE: Stop the motor.
4Example: Start/stop (1 signal) and reversal ^ 67
Funcon 2: Start enable/stop motor
•
Funcon 2 is acve if further start commands have been connected to triggers, the keypad control is acve
or the network control is acve.
TRUE: Start commands of the acve control source are enabled.
FALSE: Stop the motor.
4Example: Start forward/start reverse/stop (edge-controlled) ^ 68
4Example: Run forward/Run reverse/stop (status-controlled) ^ 70
Acvate quick stop
0x2631:003 (P400.03)
Bring the motor to a standsll in best me.
4Example: Quick stop ^ 72
Start forward (CW)
0x2631:006 (P400.06)
Start the motor edge-controlled.
•
In order to be able to start the motor, the "Run" funcon must be set to TRUE.
•
The motor is stopped by reseng the "Run" funcon to FALSE.
•
The funcons are deacvated in case of keypad or network control.
4Example: Start forward/start reverse/stop (edge-controlled) ^ 68
Start reverse (CCW)
0x2631:007 (P400.07)
Run forward (CW)
0x2631:008 (P400.08)
Let the motor rotate in a status-controlled way.
•
In order to be able to start the motor, the "Run" funcon must be set to TRUE.
•
The funcons are deacvated in the case of keypad or network control.
4Example: Run forward/Run reverse/stop (status-controlled) ^ 70
Run reverse (CCW)
0x2631:009 (P400.09)
Jog foward (CW)
0x2631:010 (P400.10)
Jog operaon: Let the motor rotate in a status-controlled way with setpoint preset.
CAUTION!
The jog operaon has a higher priority than the "Run" funcon, all other start commands and the keypad key
.
•
If the jog operaon is acve, the motor cannot be stopped with the previously menoned funcons!
•
However, jog operaon can be interrupted by the "Quick stop" funcon.
•
Jog operaon can always be acvated, even in case of keypad or network control.
4Example: Jog forward/Jog reverse ^ 74
Jog reverse (CCW)
0x2631:011 (P400.11)
Reverse rotaonal direcon
0x2631:013 (P400.13)
Invert the frequency setpoint.
•
The funcon can be used in combinaon with all start commands.
•
The funcon is deacvated in the case of network control.
4Example: Start/stop (1 signal) and reversal ^ 67
Assignment guidelines
The error message "Trigger/funcons connected incorrectly" (error code 25216 | 0x6280) is
output if one of the following assignment guidelines is not observed:
•
If the "exible I/O conguraon" is acve as control source, the "Enable inverter" or "Run"
funcon must be connected to a digital input in order that the motor can be stopped again
any me!
•
With keypad or network control, the two funcons "Enable inverter" and "Run" can also
be set to "Constant TRUE [1]" to start the motor.
•
The use of the "Start forward (CW)" and "Start reverse (CCW)" funcons excludes the use
of the "Run forward (CW)" and "Run reverse (CCW)" funcons, and vice versa.
Start, stop and rotang direcon commands
Flexible I/O conguraon of the start, stop and rotang direcon commands