10.8.7 Maximum overload current of the inverter
For the purpose of current limitaon, a maximum overload current can be set for the inverter.
If the current consumpon of the motor exceeds this current limit, the inverter changes its
dynamic behaviour, in order to counteract this exceedance.
Details
The maximum overload current of the inverter can be set in 0x6073 (P324.00).
Reference for the percentage seng of the maximum overload current is the rated motor
current set in 0x6075 (P323.00).
The actual motor current is displayed in 0x2D88 (P104.00).
If the change in the dynamic behaviour carried out by the inverter does not
result in exing the overcurrent state, the inverter outputs an error.
When 0x6078 (P103.00) (current actual value in %) exceeds 0x6073 (P324.00) (max. current
actual value in %), a message 0x238A is displayed. The status is also displayed in the following
network status word bits:
0x400C:001 bit 14
0x400C:002 bit 2
Load response Impact
Overload during acceleraon in
motor mode
A longer me is required for reaching the frequency setpoint than has been set.
Overload during deceleraon in
generator mode
A longer me than is required for reaching standsll is set.
Increasing load at constant fre-
quency
If the motor current limit value is reached:
The inverter reduces the eecve speed setpoint unl a stable working is set or an eecve speed setpoint
of 0 rpm is reached.
If the load is reduced, the inverter increases the eecve speed setpoint unl the setpoint speed is
reached or the load reaches the current limit value again.
When the generator current limit value is reached:
The inverter increases the eecve speed setpoint unl a stable working point is reached or up to the max-
imum permissible output frequency 0x2916 (P211.00).
If the load is reduced, the inverter reduces the eecve speed setpoint unl the setpoint speed is reached
or the load reaches the current limit value again.
If an abrupt load is building at the motor sha (e.g. drive is blocked), the overcurrent switch-o funcon may
respond.
Example: Overcurrent switch-o in case of a sudden load at the motor sha
0 Hz
30 Hz
10 Hz
20 Hz
40 Hz
50 Hz
60 Hz
t
0 Hz
30 Hz
10 Hz
20 Hz
40 Hz
50 Hz
60 Hz
t
0 %
100 %
t
0x6073
Motor load
Frequency setpoint selection
Output frequency
Conguring the motor control
Motor protecon
Maximum overload current of the inverter