12.3.1 Process input data
12.3.1.1 Feedback of PID variable via network
The feedback of the control variable (actual value) can also be iniated via the network for the
process controller. In this case, the following mappable parameter is available.
Parameter
Address Name / seng range / [default seng] Info
0x400B:011
(P592.11)
Process input data: PID feedback
(Process data IN: PID feedback)
-300.00 ... [0.00] ... 300.00 PID unit
From version 03.00
Mappable parameter for the feedback of the variable (actual value) via
network.
Only eecve with the selecon "Network[5]" in 0x4020:002
(P600.02).
Related topics
4Conguring the process controller ^ 116
12.3.1.2 Control digital outputs via network
The mappable data word NetWordIN2 is available for controlling the digital outputs via the
network.
Parameter
Address Name / seng range / [default seng] Info
0x4008:002
(P590.02)
Process input words: NetWordIN2
(NetWordINx: NetWordIN2)
0x0000 ... [0x0000] ... 0xFFFF
Mappable data word for oponal control of the digital outputs via net-
work.
Assignment of the digital outputs:
Relay: 0x2634:001 (P420.01) / selecon [34] ... [49]
Digital output 1: 0x2634:002 (P420.02) / selecon [34] ... [49]
Digital output 2: 0x2634:003 (P420.03) / selecon [34] ... [49]
Bit 0 Mapping bit 0
Bit 1 Mapping bit 1
Bit 2 Mapping bit 2
Bit 3 Mapping bit 3
Bit 4 Mapping bit 4
Bit 5 Mapping bit 5
Bit 6 Mapping bit 6
Bit 7 Mapping bit 7
Bit 8 Mapping bit 8
Bit 9 Mapping bit 9
Bit 10 Mapping bit 10
Bit 11 Mapping bit 11
Bit 12 Mapping bit 12
Bit 13 Mapping bit 13
Bit 14 Mapping bit 14
Bit 15 Mapping bit 15
Related topics
4Congure digital outputs ^ 263
12.3.1.3 Control analog outputs via network
The mappable data words NetWordIN3 and NetWordIN4 are available for controlling the ana-
logue outputs via the network.
Parameter
Address Name / seng range / [default seng] Info
0x4008:003
(P590.03)
Process input words: NetWordIN3
(NetWordINx: NetWordIN3)
0.0 ... [0.0] ... 100.0 %
Mappable data word for oponal control of an analog output via net-
work.
Assignment of the analog outputs:
Analog output 1: 0x2639:002 (P440.02) = "NetWordIN3 [20]"
Analog output 2: 0x263A:002 (P441.02) = "NetWordIN3 [20]"
Conguring the network
Further mappable parameters
Process input data
302