14.3 Trigger acon if a frequency threshold is exceeded
As a funcon of the current output frequency, the adjustable frequency threshold serves to
trigger a certain funcon or set a digital output.
Parameter
Address Name / seng range / [default seng] Info
0x4005
(P412.00)
Frequency threshold
(Freq. threshold)
0.0 ... [0.0] ... 599.0 Hz
Threshold for the "Frequency threshold exceeded [70]" trigger.
•
The "Frequency threshold exceeded [70]" trigger is TRUE if the cur-
rent output frequency is higher than the set threshold.
•
The trigger can be assigned to a funcon or to a digital output.
Example for operang mode
In the following example, the digital output 1 is set to TRUE if the output frequency is higher
than 20 Hz.
•
The analog input 1 is set as standard setpoint source.
•
Switch S1 starts the motor in forward direcon of rotaon. Switch S1 in the inial posion
stops the motor again.
Connecon plan Funcon
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
DO1
X3
S1
1k ...10k
0 ... 10 V
R1
Potenometer R1 Frequency setpoint selecon
Switch S1 Run
Parameter Designaon Seng for this example
0x2631:001 (P400.01) Enable inverter Constant TRUE [1]
0x2631:002 (P400.02) Run Digital input 1 [11]
0x2634:002 (P420.02) Digital outputs funcon: Digital output 1 Frequency threshold exceeded [70]
0x2824 (P200.00) Control selecon Flexible I/O conguraon [0]
0x2860:001 (P201.01) Frequency control: Default setpoint source Analog input 1 [2]
0x4005 (P412.00) Frequency threshold 20 Hz
Addional funcons
Trigger acon if a frequency threshold is exceeded