Details
•
The default seng "Flexible I/O conguraon [0]" in 0x2824 (P200.00) enables a exible
control of the inverter via digital inputs, network and keypad. The control of the inverter
via the digital inputs is precongured. For details see the subchapter "Flexible I/O congu-
raon". ^ 56
•
For details of the network control of the inverter, see the chapter "Control the inverter via
network". ^ 281
•
If the keypad is to be used as the control source for the applicaon, set "Keypad [1]" in
0x2824 (P200.00). For details, see subchapter "Keypad control". ^ 57
•
The control source that is currently acve is displayed in 0x282B:001 (P125.01).
Parameter
Address Name / seng range / [default seng] Info
0x2824
(P200.00)
Control selecon
(Control select.)
Selecon of the type of inverter control.
0 Flexible I/O conguraon This selecon enables a exible assignment of the start, stop, and rotat-
ing direcon commands with digital signal sources.
•
Digital signal sources can be digital inputs, network and keypad.
•
The I/O conguraon is made via the parameters 0x2631:xx (P400.xx).
1 Keypad This selecon enables the motor to be started exclusively via the start
key of the keypad. Other signal sources for starng the motor are
ignored.
Start motor Stop motor
Note!
•
The funcons "Enable inverter" 0x2631:001 (P400.01) and "Run"
0x2631:002 (P400.02) must be set to TRUE to start the motor.
•
If jog operaon is acve, the motor cannot be stopped via the
keypad key.
Start, stop and rotang direcon commands
Control selecon
55