Variable mapping
Via 0x232B:001 ... 0x232B:024 (P530.01 ... 24), 24 registers can be mapped to parameters
of the inverter. Format:
0xiiiiss00
(iiii = index hexadecimal,
ss = subindex hexadecimal)
The display of the internal Modbus register numbers in 0x232C:001 ... 0x232C:024
(P531.01 ... 24) is generated automacally. Since 32-bit parameters require two registers,
there is no 1:1 assignment.
For the mappable registers, a CRC (Cyclic Redundancy Check) is executed. The checksum
determined is displayed in 0x232D (P532.00). The user can read this "validaon code" and
use it for comparison in the Modbus master. In this way it can be checked whether the
inverter currently queried is congured correctly for the respecve applicaon.
Parameter
Address Name / seng range / [default seng] Info
0x232B:001 ...
0x232B:024
(P530.01 ... 24)
Modbus parameter mapping: Parameter 1 ... Parame-
ter 24
(Para. mapping: Parameter 1 ... Parameter 24)
0x00000000 ... [0x00000000] ... 0xFFFFFF00
Mapping entries for Modbus register 40103 ... 40149.
Format: 0xiiiiss00 (iiii = index, ss = subindex)
0x232C:001 ...
0x232C:024
(P531.01 ... 24)
Modbus register assignment: Register 1 ... Register 24
(Reg. assigned: Register 1 ... Register 24)
Read only
Display of the internal Modbus register number starng from which the
parameter mapped in 0x232B:001 ... 0x232B:024 (P530.01 ... 24) is
stored.
For the rst parameter mapped, always 2500.
From the second parameter mapped, 2500 + oset. The oset results
from the data types of the previously mapped parameters.
0x232D
(P532.00)
Modbus vericaon code
(Vericaoncode)
Read only
12.12.4 Monitoring
The parameters for seng network monitoring funcons are described below.
Parameter
Address Name / seng range / [default seng] Info
0x2858:001
(P515.01)
Modbus monitoring: Response to me-out
(Modbus monit.: Resp. Time-out)
Selecon of the response executed if no valid messages have been
received via the Modbus for a longer me than the me-out period set
in 0x2858:002 (P515.02).
Associated error code:
33185 | 0x81A1 - Modbus: network me-out
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
0x2858:002
(P515.02)
Modbus monitoring: Time-out me
(Modbus monit.: Time-out me)
0.0 ... [2.0] ... 300.0 s
Time-out period for monitoring the message recepon via Modbus.
Conguring the network
Modbus RTU
Monitoring
420