12.15.5 Monitoring
The inverter can give a parameterisable response to various PROFIBUS errors.
Details
The following table lists the PROFIBUS errors that can be set for a response.
Event Display in Response can be set in Default seng
Communicaon to the PROFIBUS master is connuously interrupted. 0x2349 (P517.00), Bit 0 0x2859:001 (P515.01) Fault
Data exchange via PROFIBUS has been terminated. 0x2349 (P517.00), Bit 1 0x2859:002 (P515.02) No response
The inverter has received invalid conguraon data from the master. 0x2349 (P517.00), Bit 2 0x2859:003 (P515.03) Fault
An error has occurred during the inialisaon of the PROFIBUS interface. 0x2349 (P517.00), Bit 3 0x2859:004 (P515.04) Fault
The process data received are invalid. 0x2349 (P517.00), Bit 4 0x2859:005 (P515.05) Trouble
The parameters for seng network monitoring funcons are described below.
Parameter
Address Name / seng range / [default seng] Info
0x2859:001
(P515.01)
PROFIBUS monitoring: Watchdog elapsed
(PROFIBUS monit.: WD elapsed)
Selecon of the response to the connuous interrupon of communica-
on to the PROFIBUS master, e. g. by cable break or failure of the PROFI-
BUS master.
Associated error code:
•
33168 | 0x8190 - Network: watchdog meout
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
0x2859:002
(P515.02)
PROFIBUS monitoring: Data exchange exited
(PROFIBUS monit.: Data exch.exited)
Selecon of the response to exing the "Data Exchange" state.
Associated error code:
•
33169 | 0x8191 - Network: disrupon of cyclic data exchange
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
0x2859:003
(P515.03)
PROFIBUS monitoring: Invalid conguraon
(PROFIBUS monit.: Invalid cong)
Selecon of the response triggered by the recepon of invalid congura-
on data.
Associated error code:
•
33414 | 0x8286 - Network: PDO mapping error
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
0x2859:004
(P515.04)
PROFIBUS monitoring: Inialisaon error
(PROFIBUS monit.: Init. error)
Selecon of the response triggered by the occurrence of an error during
the inialisaon of the PROFIBUS module.
Associated error code:
•
33170 | 0x8192 - Network: inialisaon error
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
0x2859:005
(P515.05)
PROFIBUS monitoring: Invalid process data
(PROFIBUS monit.: Inval. proc.data)
Selecon of the response triggered by the recepon of invalid process
data.
•
If the master changes to the "Stop" state, no cyclic process data are
sent to the inverter (slave) anymore; the length of the process data
then is 0.
Associated error code:
•
33171 | 0x8193 - Network: invalid cyclic process data
0 No response
4Error types ^ 611
1 Warning
2 Trouble
3 Fault
Conguring the network
PROFIBUS
Monitoring