18.7 3-phase mains connecon 400 V "Light Duty"
18.7.1 Rated data
The output currents apply to these operang condions:
•
At a switching frequency of 2 kHz or 4 kHz: Ambient temperature above 40 °C with a rated
output current reduced by 2.5 %/°C.
•
If the load characterisc "Light Duty" and the switching frequencies 8 kHz or 16 kHz are
selected, only the values of the load characterisc "Heavy Duty" are reached.
Inverter I55AE230F I55AE240F I55AE255F I55AE275F I55AE311F
Rated power kW 4 5.5 7.5 11 15
Rated power hp 5 7.5 10 15 20
Mains voltage range 3/PE AC 340 V ... 528 V, 45 Hz ... 65 Hz
Output voltage 3 AC 0-400/480 V
Rated mains current
Without mains choke A 10.3 14 18.3 28 -
With mains choke A 8.2 11 14.5 22 27.1
Apparent output power kVA 5.9 8 10.5 15 19
Rated output current
2 kHz A 8.8 11.9 15.6 23 28.2
4 kHz A 8.8 11.9 15.6 23 28.2
8 kHz A - - - - -
16 kHz A - - - - -
Power loss
2 kHz W 94 125 163 238 290
4 kHz W 100 133 173 253 309
8 kHz W - - - - -
16 kHz W - - - - -
For controller inhibit W 6 6 6 6 6
Cyclic mains switching 3 mes per minute
Max. Motor cable length shielded
Without EMC category m 100 100 100 100 100
Category C1 (2 kHz, 4 kHz, 8
kHz)
m - - - - -
Category C2 (2 kHz, 4 kHz, 8
kHz)
m 20 20 20 20 20
Category C3 (2 kHz, 4 kHz, 8
kHz)
m 35 35 35 50 50
Weight kg 2.3 2.3 2.3 3.7 3.7
Weight lb 5 5 5 8 8
Technical data
3-phase mains connecon 400 V "Light Duty"
Rated data
650