12.15.2.3 Suppress diagnosc messages to the master
The alarm message on the master can be oponally suppressed for certain error responses of
the inverter to facilitate suitable error handling between master and slave (inverter). Alarm
responses programmed in the master can be avoided if they are not wanted in this case.
Details
Inverter errors and warnings are sent to the Master as alarm messages. This funcon is used
to suppress, for example, the fact that the "undervoltage DC link" warning triggers an alarm
and the associated control switches to the stop mode if there is no associated alarm block or
has been programmed manually. It should be noted here, that an alarm block not program-
med in the control can pose risks to the machine. A reducon of possible alarm messages
inially helps when the machine is commissioned. Later on, however, more eort should be
made to program the alarm blocks.
Parameter
Address Name / seng range / [default seng] Info
0x285A:001 Diagnosc conguraon: Alarm supression
0 ... [0] ... 65535
•
From version 05.01
Bit coded selecon of error responses in the inverter which suppress the
alarm message to the PROFIBUS master.
•
Bit x = 1 ≡ suppress alarm message.
•
In the default seng "0", an alarm message is displayed for all error
responses.
Bit 0 Informaon
Bit 1 Warning
Bit 2 -
Bit 3 Trouble
Bit 4 -
Bit 5 -
Bit 6 -
Bit 7 Fault
Conguring the network
PROFIBUS
Basic seng and opons
461