12.10.9 Automac rmware download with Lenze Controller
The rmware of the inverter can be saved together with the »PLC Designer«- project. During
start-up, the Lenze controller checks whether the rmware version in the inverter corresponds
with the rmware version stored in the project for this device. If this is not the case, the con-
troller loads the rmware version stored in the project to the inverter. In doing so, a "device
replacement" can be ensured for service purposes, whereby the replacement device also
funcons with the same rmware version stored in the project, as the original device did pre-
viously.
Main version check
An automac rmware download from the PLC to the inverter is only undertaken under the
following condions:
Required rmware version 5.1.x.x or higher
Idencal main version 5.1.x.x.x at the inverter and in the PLC project
Restricons
Power failure during rmware download: iCIF connecon lost [33200]
In the event of a power failure, the inverter switches to a fault state. There is then only one
means for recovery:
-
Load the rmware using the Firmware-Loader via the USB diagnosc module.
-
Restart the inverter.
It may occur that the inverter switches to a fault state aer a successful rmware download.
Behaviour aer successful rmware download: interrupon of the cyclical data exchange
[33169]
-
Acknowledge the error via »PLC Designer« ,»Easy Starter« or via the mains switch.
Conguring the network
EtherCAT
Automac rmware download with Lenze Controller
394