12.10.9 Automac rmware download with Lenze Controller
The rmware of the inverter can be saved together with the »PLC Designer«- project. During
start-up, the Lenze controller checks whether the rmware version in the inverter corresponds
with the rmware version stored in the project for this device. If this is not the case, the con-
troller loads the rmware version stored in the project to the inverter. In doing so, a "device
replacement" can be ensured for service purposes, whereby the replacement device also
funcons with the same rmware version stored in the project, as the original device did pre-
viously.
Main version check
An automac rmware download from the PLC to the inverter is only undertaken under the
following condions:
•
Required rmware version 5.1.x.x or higher
•
Idencal main version 5.1.x.x.x at the inverter and in the PLC project
Restricons
Power failure during rmware download: iCIF connecon lost [33200]
In the event of a power failure, the inverter switches to a fault state. There is then only one
means for recovery:
-
Load the rmware using the Firmware-Loader via the USB diagnosc module.
-
Restart the inverter.
It may occur that the inverter switches to a fault state aer a successful rmware download.
Behaviour aer successful rmware download: interrupon of the cyclical data exchange
[33169]
-
Acknowledge the error via »PLC Designer« ,»Easy Starter« or via the mains switch.
Conguring the network
EtherCAT
Automac rmware download with Lenze Controller