6.4.2 Example: Change-over from terminal control to network control
•
The control is executed primarily via the I/O terminals. The switch S1 serves to start and
stop the motor.
•
The switch S2 serves to acvate the network control. In the case of acvated keypad con-
trol, the motor can only be started via the network control word. However, the condion is
that the switch S1 is closed.
•
If the switch S1 is opened again, the motor is stopped (irrespecve of the acve control
source).
Connecon plan Funcon
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
DO1
X3
S1 S2
1k ...10k
0 ... 10 V
R1
Potenometer R1 Frequency setpoint selecon
Switch S1 Run
Switch S2 Acvate network control
Parameter Designaon Seng for this example
0x2631:001 (P400.01) Enable inverter Constant TRUE [1]
0x2631:002 (P400.02) Run Digital input 1 [11]
0x2631:004 (P400.04) Reset fault Not connected [0]
0x2631:037 (P400.37) Acvate network control Digital input 2 [12]
0x2824 (P200.00) Control selecon Flexible I/O conguraon [0]
t
t
0 Hz
30 Hz
10 Hz
20 Hz
40 Hz
50 Hz
60 Hz
0 Hz
30 Hz
10 Hz
20 Hz
40 Hz
50 Hz
60 Hz
-40 Hz
-60 Hz
-50 Hz
-30 Hz
-20 Hz
-10 Hz
t
t
t
t
t
t
t
t
0x2DDD
Network control word: Run forward
Constant TRUE [1] Enable inverter
Digital input 2 [12]
Digital input 1 [11]
Local control active [104]
Remote control active [105]
Running [50]
Stop active [53]
Output signals
Status signals
Output frequency
Activate network control
Run
Input signals
Frequency setpoint selection
FunctionTrigger
The status signals can be assigned to digital outputs. 4Congure digital outputs ^ 263
①
When changing over to another control source, the motor is rst stopped with the stop method set in 0x2838:003 (P203.03).
②
The motor will also be stopped if the "Run" funcon is deacvated (irrespecve of the acve control source).
③
Commands via the network are ignored if the network control is not acve.
Start, stop and rotang direcon commands
Changing the control source during operaon
Example: Change-over from terminal control to network control
81