Address Name / seng range / [default seng] Info
0x2552:006
(P595.06)
Parameter access monitoring: Parameter Access Mon-
itoring-Status
(PAM monitoring: PAM status)
Read only
From version 04.00
Bit coded display of the status of parameter access monitoring.
Bit 0 Monitoring acvated 1 ≡ parameter access monitoring is acve.
Bit 1 Timeout 1 ≡ within the me-out me set in 0x2552:003 (P595.03), no successful
parameter write access to the "keep-alive register" 0x2552:002
(P595.02) was made.
Bit 2 WLAN me-out
0x2552:007
(P595.07)
Parameter access monitoring: WLAN reset me-out
me
(PAM monitoring: WLAN reset t.out)
0 ... [0] ... 65535 s
From version 05.00
Time aer which the WLAN network with the current sengs of the
WLAN parameters is restarted if no "keep alive" messages are received.
0 s = funcon deacvated (no WLAN restart).
With a seng > 0 s and a me-out, the control units sets 0x2440 =
"Restart with current values [1]".
12.5 Process data handling in the event of error
Received invalid process data is not used. The inverter uses the last valid process data
received. You can oponally set that the contents of the process data in the inverter are set to
the value "0" aer invalid process data has been received.
The seng in 0x24E5:001 is independent of the response selected in
0x2859:005 if invalid process data has been received!
If the applicaon requires that the drive keeps moving with the last valid proc-
ess data when receiving invalid process data, set the response "No response" or
"Warning" in 0x2859:005. Moreover, the selecon "Clear data [1]" must not be
set in 0x24E5:001. Deleng the process data would stop the motor.
Parameter
Address Name / seng range / [default seng] Info
0x24E5:001 Process data handling in case of error: Procedure Selecon which process data the inverter is to use aer receiving invalid
process data.
0 Keep last data The last valid process data of the master are used.
1 Clear data The contents of the process data in the inverter is set to the value "0".
Conguring the network
Process data handling in the event of error
306

Table of Contents

Other manuals for Lenze i550

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i550 and is the answer not in the manual?

Lenze i550 Specifications

General IconGeneral
Protection ClassIP20
Overload Capacity150% for 60 seconds
SafetySTO (Safe Torque Off)
Voltage Range380 V to 480 V
Control TypeVector control, V/f control
Communication InterfacesCANopen, EtherCAT, PROFINET, Ethernet/IP
Mains Voltage3-phase 380 V to 480 V
Input Voltage3-phase 380 V to 480 V
Output Voltage0 to Mains Voltage
Frequency Range0 Hz to 300 Hz
Protection FeaturesOvercurrent, overvoltage, undervoltage, short circuit, overtemperature
Ambient Temperature-10°C to 50°C

Related product manuals