Parameterisaon sequence
As soon as the parameterisaon has been started, the following steps are iniated by the
engineering tool:
1.The motor rang data and the motor equivalent circuit diagram data are loaded from the
motor catalogue.
2.The motor controller sengs and the speed controller sengs are automacally calculated
based on the previously loaded data.
Notes:
•
The data involved in this parameterisaon are provided be the motor catalogue alone. Fur-
ther user data is not required.
•
The inverter characterisc is not changed by this opmisaon.
Parameter
Address Name / seng range / [default seng] Info
0x2C01:010 Motor parameters: Motor name The name (e.g. " 1") can be freely selected by the user.
If the motor in the engineering tool has been selected from the "motor
catalog", the respecve motor name is automacally entered here
(example: "MDSKA080-22, 70").
5.8.2 Manual seng of the motor data
Manually set the motor data in accordance with the manufacturer's informaon / motor data
sheet in the following parameters, provided that an externally supplied motor is connected to
the inverter.
Parameter
Address Name / seng range / [default seng] Info
0x2910:001
(P335.01)
Motor moment of inera
(Motor inera)
0.00 ... [3.70]* ... 20000000.00 kg cm²
* Default seng depending on the size.
Seng of the moment of inera of the motor, relang to the motor.
0x2C01:001 Motor parameters: Number of pole pairs
•
Read only
Display of the number of pole pairs calculated from the rated speed and
rated frequency.
0x2C01:002 Motor parameters: Stator resistance
0.0000 ... [10.1565]* ... 125.0000 Ω
* Default seng depending on the size.
General motor data.
Carry out sengs as specied by manufacturer data/motor data sheet.
Note!
When you enter the motor nameplate data, take into account the phase
connecon implemented for the motor (star or delta connecon). Only
enter the data applying to the connecon type selected.
0x2C01:003 Motor parameters: Stator leakage inductance
0.000 ... [23.566]* ... 500.000 mH
* Default seng depending on the size.
0x2C01:004
(P320.04)
Motor parameters: Rated speed
(Motor parameters: Rated speed)
Device for 50-Hz mains: 50 ... [1450] ... 50000 rpm
Device for 60-Hz mains: 50 ... [1750] ... 50000 rpm
General motor data.
Carry out sengs as specied by motor nameplate data.
Note!
When you enter the motor nameplate data, take into account the phase
connecon implemented for the motor (star or delta connecon). Only
enter the data applying to the connecon type selected.
0x2C01:005
(P320.05)
Motor parameters: Rated frequency
(Motor parameters: Rated frequency)
Device for 50-Hz mains: 1.0 ... [50.0] ... 1000.0 Hz
Device for 60-Hz mains: 1.0 ... [60.0] ... 1000.0 Hz
0x2C01:006
(P320.06)
Motor parameters: Rated power
(Motor parameters: Rated power)
0.00 ... [0.25]* ... 655.35 kW
* Default seng depending on the size.
0x2C01:007
(P320.07)
Motor parameters: Rated voltage
(Motor parameters: Rated voltage)
0 ... [230]* ... 65535 V
* Default seng depending on the size.
0x2C01:008
(P320.08)
Motor parameters: Cosine phi
(Motor parameters: Cosine phi)
0.00 ... [0.80] ... 1.00
0x2C02:003
(P351.03)
Motor parameter (ASM): Magnesing current
(ASM motor par.: Magn. current)
0.00 ... [0.96]* ... 500.00 A
* Default seng depending on the size.
Equivalent circuit data required for the motor model of the asynchro-
nous machine.
Basic seng
Motor data
Select motor from motor catalogue
52