12.16.2.2 Suppress diagnosc messages to the IO controller
Inverter errors and warnings are sent to the IO controller as alarm messages. This funcon is
used to suppress, for example, the fact that the "undervoltage DC link" warning triggers an
alarm and the associated control switches to the stop mode if there is no associated alarm
block or has been programmed manually. It should be noted here, that an alarm block not
programmed in the control can pose risks to the machine. A reducon of possible alarm mes-
sages inially helps when the machine is commissioned. Later on, however, more eort
should be made to program the alarm blocks.
Please note that an unprogrammed alarm block in the IO controller can pose
risks to the machine. A reducon of possible alarm messages inially helps
when the machine is commissioned. Later on, however, more eort should be
made to program the alarm blocks.
0x285A:001 serves to set which error response in the inverter suppresses the alarm message
to the IO-Controller.
Parameter
Address Name / seng range / [default seng] Info
0x285A:001 Diagnosc sengs: Alarm supression
0 ... [0] ... 65535
•
From version 05.01
Bit coded selecon of error responses in the inverter which suppress the
alarm message to the IO Controller.
•
Bit x = 1 ≡ suppress alarm message.
•
In the default seng "0", an alarm message is displayed for all error
responses.
Bit 0 Informaon
Bit 1 Warning
Bit 3 Trouble
Bit 7 Fault
Conguring the network
PROFINET
Basic seng and opons
485