6.2.4 Example: Run forward/Run reverse/stop (status-controlled)
The "Run" funcon automacally becomes a "start enable" if the funcons "Run
forward (CW)"/"Run reverse (CCW)" are connected to triggers.
This example shows a status-controlled start/stop via three switches:
Switch S1 enables the start. Without start enable, the motor cannot be started.
Switch S2 starts the motor in forward direcon of rotaon.
Switch S3 starts the motor in backward direcon of rotaon.
The motor is stopped by cancelling the run commands (switches S2 and S3 open) or by
cancelling the start enable (switch S1 open).
Connecon plan Funcon
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
DO1
X3
S1 S2 S3
1k ...10k
0 ... 10 V
R1
Potenometer R1 Frequency setpoint selecon
Switch S1 Start enable
Switch S2 Run forward (CW)
Switch S3 Run reverse (CCW)
Parameter Designaon Seng for this example
0x2631:001 (P400.01) Enable inverter Constant TRUE [1]
0x2631:002 (P400.02) Run Digital input 1 [11]
0x2631:004 (P400.04) Reset fault Not connected [0]
0x2631:008 (P400.08) Run forward (CW) Digital input 2 [12]
0x2631:009 (P400.09) Run reverse (CCW) Digital input 3 [13]
0x2631:013 (P400.13) Reverse rotaonal direcon Not connected [0]
Start, stop and rotang direcon commands
Flexible I/O conguraon of the start, stop and rotang direcon commands
Example: Run forward/Run reverse/stop (status-controlled)
70