t
t
0 Hz
30 Hz
10 Hz
20 Hz
40 Hz
50 Hz
60 Hz
0 Hz
30 Hz
10 Hz
20 Hz
40 Hz
50 Hz
60 Hz
-40 Hz
-60 Hz
-50 Hz
-30 Hz
-20 Hz
-10 Hz
t
t
t
t
t
t
t
0x2DDD
Start enableRun
Digital input 2 [12] Start forward (CW)
Digital input 1 [11]
Digital input 3 [13]
Constant TRUE [1]
Stop active [53]
Rotational direction reversed [69]
Running [50]
Output signals
Status signals
Output frequency
Start reverse (CCW)
Enable inverter
Input signals
Frequency setpoint selection
FunctionTrigger
The status signals can be assigned to digital outputs. 4Congure digital outputs ^ 263
The "Run" funcon serves as start enable for the funcons "Start forward (CW)" and "Start reverse (CCW)".
Without start enable, the motor cannot be started.
If the start command is cancelled, the motor is stopped with the stop method set in 0x2838:003 (P203.03). In the example: Stop with stand-
ard ramp.
If, at start enable, "Start forward (CW)" and "Start reverse (CCW)" are already set to TRUE, the motor remains stopped and the inverter
waits for the next valid start edge.
Start, stop and rotang direcon commands
Flexible I/O conguraon of the start, stop and rotang direcon commands
Example: Start forward/start reverse/stop (edge-controlled)