8.1 Basic seng
In the following, the steps required for conguring the torque control are described.
1.
Select the motor control type SLVC/SC-ASM.
2.
Carry out motor adjustment. 4Conguring the motor control ^ 168
Set the operang mode "MS: Torque mode [-1]" in 0x6060 (P301.00).
3.
Select the standard setpoint source for the torque control in 0x2860:003 (P201.03). ^ 59.
4.
Set the rated motor torque in 0x6076 (P325.00).
5.
Set the torque limits. 4Torque limits ^ 153
6.
Set the speed
limitaon. 4Speed limitaon ^ 155
7.
Congure addional standard setpoint source. 4Congure setpoint sources ^ 158
8.
Oponal: seng of the torque setpoint ramp me 0x2948:002 (P336.02).
The following signal ow shows the internal setpoint logics:
0x6060
%
0x2860:003
MS = manufacturer specific
Torque setpoint
Motor control
Modes of operation
MS: Torque mode [-1]
Ramp time
0x2948:002
Actual torque
setpoint
0x2948:001
Positiv torque
limit source
0x2949:001
Negative torque
limit source
0x2949:002
Max torque
0x6072:000
Upper speed
limit source
0x2946:003
Lower speed
limit source
0x2946:004
Actual upper
speed limit
0x2946:007
Torque demand
0x6074:000
Torque limits
Frequency limits
The torque control with frequency limitaon is now acve and the inverter responds to the
torque setpoint given by the selected setpoint source.
Conguring the torque control
Basic seng
150