10.7.1.1 Extended sengs for idencaon
The motor must be at standsll during the calibraon. During the calibraon and aer suc-
cessful compleon of the calibraon, the blue display LED will light up permanently. As soon
as the idencaon has been performed and the device is deacvated, the LED switches to a
blinking mode. Aer that, a starng command must be triggered again to start the motor.
Required steps
Opmisaon with the keypad or an engineering tool:
1.
Trigger the parameter via the keypad or an engineering tool 0x2822:004 (P327.04).
2.
Trigger the starng command via the digital input or the keypad.
3.
The motor calibraon is performed.
4.
Issue the starng command again aer compleon.
The motor idencaon is triggered with 4 kHz by default in order to achieve beer results.
Users who do not wish to trigger the idencaon process with the 4 kHz switching frequency
can switch the conguraon bit to TRUE.
Parameter
Address Name / seng range / [default seng] Info
0x2DE0:009 Motor idencaon sengs
0 ... [0] ... 65535
•
Seng can only be changed if the inverter is inhibi-
ted.
•
From version 05.03
Seng for motor idencaon.
Bit 0 Acvate switching frequency (0x2939) Bit 0 = 0: the idencaon algorithm uses the 4 kHz switching frequency
(standard).
Bit 0 = 1: the idencaon algorithm uses the switching frequency con-
gured in the parameter 0x2939 (P305.00).
0x2DE0:010 Slip compensaon sengs
0 ... [0] ... 65535
•
Seng can only be changed if the inverter is inhibi-
ted.
•
From version 05.03
Calculaon source for torque and slip in the V/F control.
Bit 0 Via equivalent circuit diagram Bit 0 = 0: calculaon via motor data label (standard).
Bit 0 = 1: calculaon of magnesing current based on equivalent circuit
diagram (response <= SW 05.02.00).
Conguring the motor control
Opons for opmising the control loops
Automac motor idencaon (energized)
217