7.2 Congure setpoint sources
The following setpoint sources are described in this chapter:
•
Keypad ^ 86
•
Setpoint presets ^ 87
•
Motor potenometer (MOP) ^ 89
•
Sequencer ^ 91
Other setpoint source descripons can be found here:
•
Analog input 1 ^ 255
•
Analog input 2 ^ 260
•
HTL input (HTL encoder): HTL encoder ^ 162
•
HTL input (pulse train): Congure digital inputs DI3/DI4 for detecng a pulse train ^ 247
•
Network: Dene setpoint via network ^ 296
7.2.1 Keypad
For the manual setpoint selecon via keypad, the following default sengs are used:
Parameter
Address Name / seng range / [default seng] Info
0x2601:001
(P202.01)
Keypad setpoints: Frequency setpoint
(Keypad setpoints: KP freq.setpoint)
0.0 ... [20.0] ... 599.0 Hz
Default seng of the keypad setpoint for the operang mode 0x6060
(P301.00) = "MS: Velocity mode [-2]".
0x2601:002
(P202.02)
Keypad setpoints: Process controller setpoint
(Keypad setpoints: KP PID setpoint)
-300.00 ... [0.00] ... 300.00 PID unit
Default seng of the keypad setpoint for the reference value of the PID
control.
The increment for keypad setpoints can be adapted in 0x2862 (P701.00) by pressing a keypad
arrow key once.
A switch-over to the keypad during operaon is also possible as an alternave to the standard
setpoint source seng.
4Example: Change-over from AI1 setpoint to keypad setpoint ^ 136
Related topics
4Keypad ^ 550
Conguring the frequency control
Congure setpoint sources
Keypad
86