EasyManua.ls Logo

Lenze i550

Lenze i550
704 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12.6.5.4 Acvate quick stop
This command acvates quick stop when the operaon is enabled.
The drive is brought to a standsll irrespecve of the setpoint specied with the decelera-
on (0x6085 (P790.00)) set for quick stop.
A changeover to the "Quick stop acve" device status takes place.
Then, status change to the "Switch-on inhibited“ status in accordance with the default
value parameter 0x605A "Quick stop opon code".
If the operaon is not enabled (device state "Ready to switch on" or "Switched on"), this com-
mand changes the state to "".
A From all states
B Power secon inhibited (pulse inhibit)
C Power secon enabled
Bit paern in the CiA 402 control word (0x6040)
Bit 15 ... 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reserved
(specic)
Reset fault Operang mode dependent Operaon
enabled
Acvang
quick stop
Establish read-
iness for oper-
aon
Switch-on
X 0 X X X X 1 1 X
X = state is not relevant
During quick stop, the inverter executes the setpoint generaon and no longer follows the
setpoint dened by the network master.
If several inverters execute a chained synchronous moon, the quick stop funcon has to
be coordinated by the network master by means of a quick stop prole (master funcon).
In this case, quick stop cannot be acvated via the control bit 2.
During the quick stop, the current limit (0x6073 (P324.00)) and the torque limit (0x6072
(P326.00)) are acve. The lower of the two limits determines the motor output torque.
The torque limits from 0x60E0 and 0x60E1 are not eecve during the quick stop.
Conguring the network
Device prole CiA 402
Commands for device state control
314

Table of Contents

Other manuals for Lenze i550

Related product manuals