Parameter
Address Name / seng range / [default seng] Info
0x2838:001
(P203.01)
Start/stop conguraon: Start method
(Start/stop confg: Start method)
•
Seng can only be changed if the inverter is inhibi-
ted.
Response aer starng command.
0 Normal Aer start command, the standard ramps are acve.
•
Acceleraon me 1 can be set in 0x2917 (P220.00).
•
Deceleraon me 1 can be set in 0x2918 (P221.00).
1 DC braking Aer start command, the "DC braking" funcon is acve for the me set
in 0x2B84:002 (P704.02).
4DC braking^ 196
CAUTION!
Deacvate automac DC braking, if a holding brake is used.
2 Flying restart circuit Aer the start command, the ying restart circuit is acve.
The ying restart funcon makes it possible to restart a coasng motor
during operaon without speed feedback. The course between the
inverter and motor is coordinated so that the transion to the rotang
motor is eected without jerk at the me of connecon.
4Flying restart circuit^ 188
3 Pre-magnesaon (from version 05.03) This seng corresponds to the seng [0] Normal, but adds the premag-
nesaon of the motor before the rotaon/acceleraon begins. The pre-
magnesaon can reduce the motor current during the acceleraon and
generate a more even acceleraon curve (by avoiding overcurrent situa-
ons).
The premagnesaon funcon is relevant when operang in V/f motor
control modes. The premagnesaon causes a slight delay before the
motor acceleraon begins (typically 50-200 ms, depending on motor
characterisc).
0x2838:002
(P203.02)
Start/stop conguraon: Start at power-up
(Start/stop confg: Start at powerup)
Starng performance aer switching on the mains voltage.
0 O No automac start aer switching on mains voltage. In addion to the
inverter enable, a renewed start command is always required to start the
motor.
1 On Automac start of the motor aer switching on the mains voltage if the
inverter is enabled and a start command exists.
Related topics
4Start, stop and rotang direcon commands ^ 54
Basic seng
Starng performance
45