30355 0x7693 EPM data: PU size incompable Keypad display: EPM PU size inco
Cause Error type/response Remedy
The parameter sengs saved in the memory
module are incompable with the inverter.
Fault
•
The data have been loaded into the RAM
memory, but they are incompable.
1.
Execute device command "Load default set-
tings" 0x2022:001 (P700.01).
2.
Execute "Save user data" 0x2022:003
(P700.03) or "Save OEM data" 0x2022:006
(P700.06) device command.
30356 0x7694 EPM data: new PU size detected Keypad display: EPM new PU size
Cause Error type/response Remedy
The parameter sengs saved in the memory
module comply with a dierent hardware.
Example: Memory module of an inverter with a
power of 3 kW is used in an inverter with a
power of 18.5 kW.
Fault
•
The data have been loaded into the RAM
memory without being modied, and they
are compable.
•
The sengs loaded must be accepted by the
user (see remedy).
1.
Check parameter sengs.
2.
Reset error.
3.
Execute "Save user data" 0x2022:003
(P700.03) or "Save OEM data" 0x2022:006
(P700.06) device command.
30357 0x7695 Invalid parameter changeover conguraon Keypad display: InvalidChgovrCfg
Cause Error type/response Remedy
One or more parameters can no longer be used
for the "Parameter change-over" funcon.
Warning
•
The parameter change-over funcon is deac-
vated.
1.
Check error message for parameter change-
over in 0x4047:001 (P756.01).
2.
Correct the list entry shown in 0x4047:002
(P756.02).
30358 0x7696 EPM data: unknown parameter found Keypad display: Unkn. Par in EPM
Cause Error type/response Remedy
The memory module contains parameter set-
tings for one or several parameters that are not
known to the inverter.
Informaon Execute the "Save user data" 0x2022:003
(P700.03) device command. This reinialises
the user memory with the current parameter
sengs. In this way, parameter sengs that are
no longer required are automacally deleted.
30359 0x7697 Parameter changes lost Keypad display: Parameter loss
Cause Error type/response Remedy
A voltage failure has occurred and changed
parameter sengs that had not been saved yet
were available.
Fault
•
The parameter sengs changed have been
lost.
1.
Execute parameter sengs again.
2.
Execute device command "Save user data"
0x2022:003 (P700.03).
33042 0x8112 Network: meout explicit message Keypad display: TO expl. msg
Cause Error type/response Remedy
•
Within the me-out period for explicit mes-
sages, which has been parameterised by the
scanner, no "explicit message" was received.
•
The connecon to the scanner has been
interrupted.
•
Failure of an explicit connecon.
Warning (Congurable)
•
Check cables and terminals.
•
Plug network cables into the Ethernet port.
•
Check the requested package interval (RPI) of
the explicit connecon.
•
Increase me limit for explicit messages in
the scanner.
Seng parameters: 0x2859:006 (P515.06)
Diagnoscs and fault eliminaon
Error codes, causes and remedies