CIP Generic Master(read/write assembly data)
For "CIP Generic Master" that do not support the Implicit Messaging (class 1), the assembly
data can be read or wrien via Explicit Messaging (class 3).
Denions to read assembly data (Adapter à Scanner):
Message Type = CIP Generic
Service Code = 0x0E (read assembly data, Get_Aribute_Single)
Class= 0x04
Instance= assembly number in the desired device (e. g. 73 for assembly "73")
Aribute= 0x03
Desnaon Element= target array in the PLC (scanner) for the assembly data to be read.
The array must have the INT format and the same data length as the desired assembly!
Denions to write assembly data (Scanner à Adapter):
Message Type = CIP Generic
Service Code = 0x10 (write assembly data, Set_Aribute_Single)
Class= 0x04 (hex)
Instance= assembly number in the desired device (e. g. 23 for assembly "23")
Aribute= 0x03
Source Element = INT array in the PLC (scanner), that is used as source of the assembly
data to be wrien.
Source Length= data length (bytes) of the INT array to be wrien (the assembly "23" con-
tains e. g. 3 words which corresponds to 6 bytes.)
Explicit Message Path
For each explicit message, the path must be specied in order to forward the message from
the Ethernet port of the PLC (scanner) to the IP address of the inverter (adapter). This path
depends on the used PLC. If required, contact the PLC manufacturer to nd out how the path
is specied.
Explicit Messaging Timeout
In order to prevent that the inverter runs connuously, a me-out error state can be set.
For this purpose, set these parameters:
0x23A1:010 (P510.10): Timeout
0x2859:007 (P515.07): Timeout communicaon
Conguring the network
EtherNet/IP
Parameter data transfer