EasyManua.ls Logo

Lenze i550

Lenze i550
704 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Address Name / seng range / [default seng] Info
0x2631:039
(P400.39)
Funcon list: Acvate ramp 2
(Funcon list: Acv. ramp 2)
Further seng opons: 4Trigger list ^ 64
Assignment of a trigger for the "Acvate ramp 2" funcon.
Trigger = TRUE: acvate acceleraon me 2 and deceleraon me 2
manually.
Trigger = FALSE: no acon / deacvate funcon again.
Notes:
If the funcon is used and the assigned trigger = TRUE, the auto
change-over threshold 0x291B (P224.00) for ramp 2 is deacvated.
Acceleraon me 2 can be set in 0x2919 (P222.00).
Deceleraon me 2 can be set in 0x291A (P223.00).
0 Not connected No trigger assigned (trigger is constantly FALSE).
Example for operang mode
Switch S1 starts the motor in forward direcon of rotaon. Switch S1 in the inial posion
stops the motor again.
Switch S2 acvates the acceleraon me 2 and deceleraon me 2.
Connecon plan Funcon
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
DO1
X3
S1 S2
1k ...10k
0 ... 10 V
R1
Potenometer R1 Frequency setpoint selecon
Switch S1 Run
Switch S2 Acvate ramp 2
Parameter Designaon Seng for this example
0x2631:001 (P400.01) Enable inverter Constant TRUE [1]
0x2631:002 (P400.02) Run Digital input 1 [11]
0x2631:004 (P400.04) Reset fault Not connected [0]
0x2631:039 (P400.39) Acvate ramp 2 Digital input 2 [12]
0x2824 (P200.00) Control selecon Flexible I/O conguraon [0]
0x2838:003 (P203.03) Stop method Standard ramp [1]
0x2860:001 (P201.01) Frequency control: Default setpoint source Analog input 1 [2]
0x2917 (P220.00) Acceleraon me 1 10.0 s
0x2918 (P221.00) Deceleraon me 1 10.0 s
0x2919 (P222.00) Acceleraon me 2 5.0 s
0x291A (P223.00) Deceleraon me 2 5.0 s
Conguring the frequency control
Change over to ramp 2 during operaon
144

Table of Contents

Other manuals for Lenze i550

Related product manuals