Address Name / seng range / [default seng] Info
0x2631:047
(P400.47)
Funcon list: Inhibit process controller I-component
(Funcon list: PID-I inhibited)
•
Further seng opons: 4Trigger list ^ 64
Assignment of a trigger for the "Inhibit process controller I-component"
funcon.
Trigger = TRUE: If PID control is acvated, the I component of the PID
controller is set to 0 and the integraon process is stopped.
Trigger = FALSE: no acon / deacvate funcon again.
Notes:
•
The reset me can be set in 0x4049 (P602.00).
0 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:048
(P400.48)
Funcon list: Acvate PID inuence ramp
(Funcon list: PID-Inf ramp on)
•
Further seng opons: 4Trigger list ^ 64
Assignment of a trigger for the "Acvate PID inuence ramp" funcon.
Trigger = TRUE: the inuence of the process controller is shown via a
ramp.
Trigger = FALSE or not connected: the inuence of the process controller
is hidden via ramp.
Notes:
•
The inuence of the process controller is always acve (not only when
PID control is acvated).
•
Acceleraon me for showing the inuence of the process controller
can be set in 0x404C:001 (P607.01).
•
Deceleraon me for hiding the inuence of the process controller
can be set in 0x404C:002 (P607.02).
1 Constant TRUE Trigger is constantly TRUE.
Example for operang mode
In the following example, the "Deacvate PID controller" funcon is used to deacvate the
PID control temporarily:
•
As standard setpoint source, the frequency preset 1 is set to 20 Hz.
•
The switch S1 starts the motor in the forward direcon of rotaon. The switch S1 in the
inial posion stops the motor again.
•
The switch S2 deacvates the PID control. The motor is then driven in a speed-controlled
way.
Connecon plan Funcon
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
DO1
X3
S1 S2
Switch S1 Run
Switch S2 Deacvate PID controller
Parameter Designaon Seng for this example
0x2631:001 (P400.01) Enable inverter Constant TRUE [1]
0x2631:002 (P400.02) Run Digital input 1 [11]
0x2631:004 (P400.04) Reset fault Not connected [0]
0x2631:045 (P400.45) Deacvate PID controller Digital input 2 [12]
0x2824 (P200.00) Control selecon Flexible I/O conguraon [0]
0x2838:003 (P203.03) Stop method Standard ramp [1]
0x2860:001 (P201.01) Frequency control: Default setpoint source Frequency preset 1 [11]
0x2911:001 (P450.01) Frequency setpoint presets: Preset 1 20 Hz
0x2916 (P211.00) Maximum frequency 50 Hz
The example assumes that the process controller has been congured accord-
ingly. 4Basic seng ^ 117
Conguring the frequency control
Conguring the process controller
Process controller funcon selecon