Address Name / seng range / [default seng] Info
0x2631:047
(P400.47)
Funcon list: Inhibit process controller I-component
(Funcon list: PID-I inhibited)
Further seng opons: 4Trigger list ^ 64
Assignment of a trigger for the "Inhibit process controller I-component"
funcon.
Trigger = TRUE: If PID control is acvated, the I component of the PID
controller is set to 0 and the integraon process is stopped.
Trigger = FALSE: no acon / deacvate funcon again.
Notes:
The reset me can be set in 0x4049 (P602.00).
0 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:048
(P400.48)
Funcon list: Acvate PID inuence ramp
(Funcon list: PID-Inf ramp on)
Further seng opons: 4Trigger list ^ 64
Assignment of a trigger for the "Acvate PID inuence ramp" funcon.
Trigger = TRUE: the inuence of the process controller is shown via a
ramp.
Trigger = FALSE or not connected: the inuence of the process controller
is hidden via ramp.
Notes:
The inuence of the process controller is always acve (not only when
PID control is acvated).
Acceleraon me for showing the inuence of the process controller
can be set in 0x404C:001 (P607.01).
Deceleraon me for hiding the inuence of the process controller
can be set in 0x404C:002 (P607.02).
1 Constant TRUE Trigger is constantly TRUE.
Example for operang mode
In the following example, the "Deacvate PID controller" funcon is used to deacvate the
PID control temporarily:
As standard setpoint source, the frequency preset 1 is set to 20 Hz.
The switch S1 starts the motor in the forward direcon of rotaon. The switch S1 in the
inial posion stops the motor again.
The switch S2 deacvates the PID control. The motor is then driven in a speed-controlled
way.
Connecon plan Funcon
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
DO1
X3
S1 S2
Switch S1 Run
Switch S2 Deacvate PID controller
Parameter Designaon Seng for this example
0x2631:001 (P400.01) Enable inverter Constant TRUE [1]
0x2631:002 (P400.02) Run Digital input 1 [11]
0x2631:004 (P400.04) Reset fault Not connected [0]
0x2631:045 (P400.45) Deacvate PID controller Digital input 2 [12]
0x2824 (P200.00) Control selecon Flexible I/O conguraon [0]
0x2838:003 (P203.03) Stop method Standard ramp [1]
0x2860:001 (P201.01) Frequency control: Default setpoint source Frequency preset 1 [11]
0x2911:001 (P450.01) Frequency setpoint presets: Preset 1 20 Hz
0x2916 (P211.00) Maximum frequency 50 Hz
The example assumes that the process controller has been congured accord-
ingly. 4Basic seng ^ 117
Conguring the frequency control
Conguring the process controller
Process controller funcon selecon
127