25265 0x62B1 NetWordIN1 conguraon incorrect Keypad display: NetWordIN1 error
Cause Error type/response Remedy
Two bits of the NetWordIN1 data word
0x4008:001 (P590.01) were assigned to the
same funcon.
Trouble Check and correct conguraon of the NetWor-
dIN1 data word.
•
The funcons that are to be triggered via
bits 0 ... 15 of the NetWordIN1 data word are
dened in 0x400E:001 (P505.01) ... 0x400E:
016 (P505.16).
Related topics
4Dene your own control word format ^ 284
25505 0x63A1 CU: load error ID tag Keypad display: CU ID tag error
Cause Error type/response Remedy
Calibraon data of the control unit not compa-
ble or faulty.
Fault
•
The inverter is inhibited immediately. The
motor becomes torqueless (coasts).
•
The error can only be reset by mains switch-
ing.
•
Update rmware of the inverter to the most
recent version.
•
If the error persists, the control unit or the
device has to be replaced. In this case, please
contact the manufacturer.
25506 0x63A2 PU: load error ID tag Keypad display: PU ID tag error
Cause Error type/response Remedy
Calibraon data of the power unit not compa-
ble or faulty.
Fault
•
The inverter is inhibited immediately. The
motor becomes torqueless (coasts).
•
The error can only be reset by mains switch-
ing.
•
Update rmware of the inverter to the most
recent version.
•
If the error persists, the power unit or the
device has to be replaced. In this case, please
contact the manufacturer.
25507 0x63A3 Power unit unknown Keypad display: PU unknown
Cause Error type/response Remedy
The power unit installed is not supported by the
soware.
Fault
•
The inverter is inhibited immediately. The
motor becomes torqueless (coasts).
•
The error can only be reset by mains switch-
ing.
Update rmware of the inverter to the most
recent version.
28800 0x7080 Asseron level monitoring (Low/High) Keypad display: Asseronlevel
Cause Error type/response Remedy
The last seng of the connecon level diers
from the saved seng.
Fault
1.
Check seng in 0x2630:001 (P410.01).
2.
Execute device command "Save user data"
0x2022:003 (P700.03).
3.
Switch inverter o and on again.
28801 0x7081 Analog input 1 fault Keypad display: AI1 fault
Cause Error type/response Remedy
The monitoring funcon of the input signal con-
gured for analog input 1 in 0x2636:008
(P430.08) and 0x2636:009 (P430.09) has been
triggered.
Fault (Congurable)
•
Check input signal at analog input 1.
•
Check conguraon of the monitoring func-
on.
Seng parameters: 0x2636:010 (P430.10)
Related topics
4Analog input 1 ^ 255
Diagnoscs and fault eliminaon
Error codes, causes and remedies
624