Address Name / seng range / [default seng] Info
0x2635:003
(P421.03)
Inversion of digital outputs: Digital output 2
(DO inversion: DO2 inversion)
•
Only available for applicaon I/O.
Inversion of digital output 2
0 Not inverted
1 Inverted
0x4017:003 Digital output 2: Cutout delay
0.000 ... [0.000] ... 65.535 s
•
Only available for applicaon I/O.
Switch-o delay for digital output 2.
Note!
The set delay me is not eecve (internally set to "0") if the relay is
assigned to the trigger "Release holding brake [115]". Only the decelera-
on me set in 0x2820:012 (P712.12)for closing the holding brake inu-
ences the me-dependent behaviour of the digital output.
0x4017:004 Digital output 2: Switch-on delay
0.000 ... [0.000] ... 65.535 s
•
Only available for applicaon I/O.
Switch-on delay for digital output 2.
Note!
The set delay me is not eecve (internally set to "0") if the relay is
assigned to the trigger "Release holding brake [115]". Only the decelera-
on me set in 0x2820:012 (P712.12)for closing the holding brake inu-
ences the me-dependent behaviour of the digital output.
0x4017:005 Digital output 2: Terminal state
•
Read only
•
Only available for applicaon I/O.
Display of the logic state of output terminal X3/DO2.
0 FALSE
1 TRUE
0x4017:006 Digital output 2: Trigger signal state
•
Read only
•
Only available for applicaon I/O.
Display of the logic state of the trigger signal for digital output 2 (without
taking a ON/OFF delay set and inversion into consideraon).
0 FALSE
1 TRUE
I/O extensions and control connecons
Congure digital outputs
Digital output 2