Address Name / seng range / [default seng] Info
0x2634:016
(P420.16)
Digital outputs funcon: NetWordOUT1 - bit 6
(Dig.out.funcon: NetWordOUT1.06)
•
For further possible sengs, see parameter
0x2634:001 (P420.01). ^ 263
Assignment of a trigger to bit 6 of NetWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
50 Running TRUE if inverter and start are enabled and output frequency > 0.2 Hz.
Otherwise FALSE.
0x2634:017
(P420.17)
Digital outputs funcon: NetWordOUT1 - bit 7
(Dig.out.funcon: NetWordOUT1.07)
•
For further possible sengs, see parameter
0x2634:001 (P420.01). ^ 263
Assignment of a trigger to bit 7 of NetWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
58 Device warning acve TRUE if warning is acve. Otherwise FALSE.
•
A warning has no impact on the operang status of the inverter.
•
A warning is reset automacally if the cause has been eliminated.
0x2634:018
(P420.18)
Digital outputs funcon: NetWordOUT1 - bit 8
(Dig.out.funcon: NetWordOUT1.08)
•
For further possible sengs, see parameter
0x2634:001 (P420.01). ^ 263
Assignment of a trigger to bit 8 of NetWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
0 Not connected No trigger assigned (trigger is constantly FALSE).
0x2634:019
(P420.19)
Digital outputs funcon: NetWordOUT1 - bit 9
(Dig.out.funcon: NetWordOUT1.09)
•
For further possible sengs, see parameter
0x2634:001 (P420.01). ^ 263
Assignment of a trigger to bit 9 of NetWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
0 Not connected No trigger assigned (trigger is constantly FALSE).
0x2634:020
(P420.20)
Digital outputs funcon: NetWordOUT1 - bit 10
(Dig.out.funcon: NetWordOUT1.10)
•
For further possible sengs, see parameter
0x2634:001 (P420.01). ^ 263
Assignment of a trigger to bit 10 of NetWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
72 Setpoint speed reached TRUE if frequency setpoint reached. Otherwise FALSE.
0x2634:021
(P420.21)
Digital outputs funcon: NetWordOUT1 - bit 11
(Dig.out.funcon: NetWordOUT1.11)
•
For further possible sengs, see parameter
0x2634:001 (P420.01). ^ 263
Assignment of a trigger to bit 11 of NetWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
78 Current limit reached
TRUE if current motor current ≥ maximum current. Otherwise FALSE.
•
Display of the present motor current in 0x2D88 (P104.00).
•
Seng for the maximum current in 0x6073 (P324.00).
0x2634:022
(P420.22)
Digital outputs funcon: NetWordOUT1 - bit 12
(Dig.out.funcon: NetWordOUT1.12)
•
For further possible sengs, see parameter
0x2634:001 (P420.01). ^ 263
Assignment of a trigger to bit 12 of NetWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
71 Actual speed = 0
TRUE if current output frequency = 0 Hz (± 0.01 Hz), irrespecve of the
operang mode. Otherwise FALSE.
•
Display of the current output frequency in 0x2DDD (P100.00).
0x2634:023
(P420.23)
Digital outputs funcon: NetWordOUT1 - bit 13
(Dig.out.funcon: NetWordOUT1.13)
•
For further possible sengs, see parameter
0x2634:001 (P420.01). ^ 263
Assignment of a trigger to bit 13 of NetWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
69 Rotaonal direcon reversed TRUE if output frequency is negave. Otherwise FALSE.
0x2634:024
(P420.24)
Digital outputs funcon: NetWordOUT1 - bit 14
(Dig.out.funcon: NetWordOUT1.14)
•
For further possible sengs, see parameter
0x2634:001 (P420.01). ^ 263
Assignment of a trigger to bit 14 of NetWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
115 Release holding brake Trigger signal for releasing the holding brake (TRUE = release holding
brake).
Note!
If this trigger is assigned to the relay or a digital output, the deceleraon
mes set for the respecve output are not eecve (are internally set to
"0"). Only the deceleraon me set in 0x2820:012 (P712.12) for closing
the holding brake inuences in this case the me-dependent behaviour
of the output.
4Holding brake control^ 203
Conguring the network
Control the inverter via network
Dene your own status word format
293