Save the »RSLogix™« project and load the conguraon into the PLC (scanner):
1.»RSLogix™«project must be saved.
Click "File" in the upper toolbar and execute the "Save" menu command.
If the project is saved for the rst me, the "Save as" dialog box appears. Here, navigate to a
folder, enter a lename, and click on "Save".
The conguraon is saved in a le on your PC.
2.Load conguraon into the scanner.
a) Click "Communicaons" in the upper toolbar and execute the "Download" menu com-
mand.
The "Download" dialog box is opened.
b) Click "Download".
The conguraon is loaded into the scanner.
If the download has been completed successfully, »RSLogix™« changes to the online
mode and the I/O-OK eld in the upper le area of the screen is green.
Control the inverter via the network
In the default seng, the digital input DI1 is assigned the "Run" funcon. If the
network control is acvated, this funcon serves as "start enable" for start com-
mands via network. Hence, the digital input DI1 must be set to the HIGH level in
order that the motor can be started via the network.
4Flexible I/O conguraon of the start, stop and rotang direcon com-
mands ^ 59
In order that the inverter can be controlled via the network, acvate the network control:
0x2631:037 (P400.37) = "Network control acve [114]"
Select "Network [5]" in 0x2860:001 (P201.01) to use the network generally as a standard set-
point source. If another standard setpoint source is set, a change-over to the network setpoint
via the AC Drive control word 0x400B:001 (P592.01) is possible in case the network control is
acvated:
Change-over to network setpoint
The network setpoint is acvated via bit 6 (NetRef) of the AC Drive control word:
Bit 6 Selecon:
0 Standard setpoint source selected in 0x2860:001 (P201.01).
1 Network setpoint
Note!
In order that the acvaon via bit 6 works, the selecon "Network setpoint acve [116]" must be set in 0x2631:017 (P400.17).
Oponally, a change-over from the standard setpoint source to the network setpoint is also
possible via a digital input:
Set a standard setpoint source dierent than Network" [5]" in 0x2860:001 (P201.01).
Set the desired digital input in 0x2631:017 (P400.17) via which the change-over to the net-
work setpoint is to take place.
Bits 5 (NetCtrl) and 6 (NetRef) of byte 0 in the assembly output objects 21 and
23 must be transmied to the inverter in order that control and speed reference
commands are accepted by the network.
If the network control is acve (0x400B:001 (P592.01)/bit 5 = 1 and 0x2631:037
(P400.37) = 114), all bits of the AC drive control word (0x400B:001 (P592.01))
are processed.
If the network control is not acve (0x400B:001 (P592.01)/bit 5 = 0 or
0x2631:037 (P400.37) = 0), the control bits 0, 1, 12, 13, 14, 15 are not pro-
cessed. Their states are ignored and the drive is in local control.
Conguring the network
EtherNet/IP
Commissioning
397