Address Name / seng range / [default seng] Info
0x2323
(P509.00)
Modbus switch posion
(Modbus switch)
•
Read only
Display of the DIP switch seng at the last mains power-on.
•
The value displayed corresponds to the sum of all DIP switch values
(except for DIP switches for terminang resistor).
0x232A:001
(P580.01)
Modbus stascs: Messages received
(Modbus stasc: Mess. received)
•
Read only
Display of the total number of messages received.
•
This counter counts both valid and invalid messages.
•
Aer the maximum value has been reached, the counter starts again
"0".
0x232A:002
(P580.02)
Modbus stascs: Valid messages received
(Modbus stasc: Val. mess. rec.)
•
Read only
Display of the number of valid messages received.
•
Aer the maximum value has been reached, the counter starts again
"0".
0x232A:003
(P580.03)
Modbus stascs: Messages with excepons
(Modbus stasc: Mess. w. exc.)
•
Read only
Display of the number of messages with excepons that have been
received.
•
Aer the maximum value has been reached, the counter starts again
"0".
0x232A:004
(P580.04)
Modbus stascs: Messages with errors
(Modbus stasc: Mess. w. errors)
•
Read only
Display of the number of messages received with a faulty data integrity
(parity, CRC).
•
Aer the maximum value has been reached, the counter starts again
"0".
0x232A:005
(P580.05)
Modbus stascs: Messages sent
(Modbus stasc: Messages sent)
•
Read only
Display of the total number of messages sent.
•
Aer the maximum value has been reached, the counter starts again
"0".
0x232E:001
(P583.01)
Modbus diagnoscs of last Rx data: Oset
(Rx data diagn.: Rx data oset)
0 ... [0] ... 240
For purposes of diagnoscs, the last message received (max. 16 bytes) is
shown in 0x232E:002 (P583.02)...0x232E:017 (P583.17). For longer mes-
sages, an oset can be specied here, indicang from which byte of the
message the display of the 16 bytes is to start.
Conguring the network
Modbus RTU
Diagnoscs