Sengs in the »Siemens TIA Portal«
Here, commissioning with the »Siemens TIA Portal« is described.
Please note that in the standard seng of the »Siemens TIA Portal« changes of
network parameters carried out by a Lenze engineering tool
(e. g. »EASY Starter«) may be overwrien.
1.
Go to the device conguraon and open the "net view" to drag the inverter from the cata-
log to the net view of the PROFINET.
2.
Assign the inverter to the associated IO-Controller.
3.
Mark the inverter and change to the "device view".
4.
Set the IP address and the staon name ("PROFINET device name") in "Properes".
In order that the inverter can be idened via Ethernet when the IO controller is
switched o, it is necessary that the IP address is saved in the inverter with
mains failure protecon via the separate entry with the »EASY Starter«.
Use the 0x2022:003 (P700.03) parameter to save the sengs. More informa-
on: 4Saving the parameter sengs ^ 37
5.
Below the module name and the name of the device descripon le, the device view
shows the pre-assignment of three output and input process data words:
•
Addional process data words can be added or pre-allocated process data words can
be changed in the device view.
•
The length of the process data can be selected based on the GSDML device descripon
le.
•
All addresses of the input and output data words must follow each other without inter-
rupon.
•
Observe the
informaon about data mapping and the example below:
6.
Save the project in the engineering tool.
7.
Load the
conguraon into the IO-Controller.
8.
Place the IO-Controller in "RUN", e. g. by seng bit 4 in the NetWordIN1 control word
(0x400E:005 (P505.05)).
•
The start-up causes the current conguraon to be transferred to the inverter.
•
If required, save mapping and all other parameters in the inverter with 0x2022:003
(P700.03) with mains failure protecon, see 4Saving the parameter sengs ^ 37
Conguring the network
PROFINET
Commissioning
482