Parameter Designaon Default seng
Control funcons
①
0x2631:002 (P400.02) Run Digital input 1 [11]
②
0x2631:004 (P400.04) Reset fault Digital input 2 [12]
③
0x2631:013 (P400.13) Reverse rotaonal direcon Digital input 3 [13]
④
0x2631:018 (P400.18) Acvate preset (bit 0) Digital input 4 [14]
⑤
0x2631:019 (P400.19) Acvate preset (bit 1) Digital input 5 [15]
Conguraon of digital outputs
⑥
0x2634:001 (P420.01) Relay Ready for operaon [51]
⑦
0x2634:002 (P420.02) Digital output 1 Release holding brake [115]
⑧
0x2634:003 (P420.03) Digital output 2 (only for applicaon I/O) Fault acve [56]
Sengs for the frequency setpoint
⑨
0x2860:001 (P201.01) Frequency control: Default setpoint source Analog input 1 [2]
⑩
0x2911:001 (P450.01) Frequency setpoint presets: Preset 1 20 Hz
⑪
0x2911:002 (P450.02) Frequency setpoint presets: Preset 2 40 Hz
⑫
0x2911:003 (P450.03) Frequency setpoint presets: Preset 3 50 Hz
⑬
0x2917 (P220.00) Acceleraon me 1 5.0 s
⑭
0x2918 (P221.00) Deceleraon me 1 5.0 s
All funconal possible sengs for controlling the inverter are described in the "Start, stop
and rotang direcon commands" chapter. ^ 54
Basic seng
Funcon assignment of the inputs and outputs (default seng)
49