EasyManua.ls Logo

Lenze i550

Lenze i550
704 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Designaon Default seng
Control funcons
0x2631:002 (P400.02) Run Digital input 1 [11]
0x2631:004 (P400.04) Reset fault Digital input 2 [12]
0x2631:013 (P400.13) Reverse rotaonal direcon Digital input 3 [13]
0x2631:018 (P400.18) Acvate preset (bit 0) Digital input 4 [14]
0x2631:019 (P400.19) Acvate preset (bit 1) Digital input 5 [15]
Conguraon of digital outputs
0x2634:001 (P420.01) Relay Ready for operaon [51]
0x2634:002 (P420.02) Digital output 1 Release holding brake [115]
0x2634:003 (P420.03) Digital output 2 (only for applicaon I/O) Fault acve [56]
Sengs for the frequency setpoint
0x2860:001 (P201.01) Frequency control: Default setpoint source Analog input 1 [2]
0x2911:001 (P450.01) Frequency setpoint presets: Preset 1 20 Hz
0x2911:002 (P450.02) Frequency setpoint presets: Preset 2 40 Hz
0x2911:003 (P450.03) Frequency setpoint presets: Preset 3 50 Hz
0x2917 (P220.00) Acceleraon me 1 5.0 s
0x2918 (P221.00) Deceleraon me 1 5.0 s
All funconal possible sengs for controlling the inverter are described in the "Start, stop
and rotang direcon commands" chapter. ^ 54
Basic seng
Funcon assignment of the inputs and outputs (default seng)
49

Table of Contents

Other manuals for Lenze i550

Related product manuals