Address Name / seng range / [default seng] Info
0x2389:002
(P517.02)
PROFINET error: Error 2
(PROFINET error: Error2)
Read only
From version 02.00
The parameter currently contains the error detected on the network.
The error values may occur in combinaon with the error values from
parameter 0x2389:001 (P517.01).
Bit 7 IP address error The IP address is invalid. Valid IP addresses are dened according to RFC
3330.
Bit 8 Staon name problem The staon name must be assigned according to the PROFINET specica-
on.
Bit 9 DataExch le PROFINET communicaon is connuously interrupted in the
"Data_Exchange" state, e. g. by cable break.
PROFINET communicaon changes to the "No_Data_Exchange" state.
When the watchdog monitoring me specied by the IO Controller
has elapsed, the response set in is triggered in the inverter.
Bit 10 Stack boot error
Bit 11 Stack online error
Bit 12 Stack state error
Bit 13 Stack revision error
Bit 14 Inializaon problem The stack cannot be iniated with the user specicaons. A reason
might be, e. g., a staon name that does not correspond to the PROFI-
NET specicaon.
Bit 15 Stack init error
Conguring the network
PROFINET
Diagnoscs
494