Address Name / seng range / [default seng] Info
0x2631:042
(P400.42)
Funcon list: Select parameter set (bit 1)
(Funcon list: Sel. paramset b1)
•
Seng can only be changed if the inverter is inhibi-
ted.
•
Further seng opons: 4Trigger list ^ 64
Assignment of a trigger for the "Select parameter set (bit 1)" funcon.
Selecon bit with the valency 2
1
for "Parameter change-over" funcon.
Trigger = FALSE: selecon bit = "0".
Trigger = TRUE: selecon bit = "1".
0 Not connected No trigger assigned (trigger is constantly FALSE).
0x4046
(P755.00)
Acvaon of parameter set
(PSet acvaon)
Selecon of the acvaon method for the parameter change-over.
•
If the selecon is changed from "Via command... [0]/[1]" to "If the
selecon is changed...[2]/[3]" aer switch-on, the parameter set
selected via the funcons "Select parameter set (bit 0)" and "Select
parameter set (bit 1)" is acvated immediately. In case of selecon
[2], however, this only takes place if the inverter is disabled, the motor
is stopped or an error is acve.
0 Via command (disable required) The parameter set selected via the funcons "Select parameter set (bit
0)" and "Select parameter set (bit 1)" is acvated if the trigger assigned
to the "Load parameter set" funcon in 0x2631:040 (P400.40) provides a
FALSE-TRUE edge AND the inverter is inhibited, the motor is stopped or
an error is acve.
4Example: Acvaon via command (only when disabled)^ 532
1 Via command (immediately) The parameter set selected via the funcons "Select parameter set (bit
0)" and "Select parameter set (bit 1)" is immediately acvated if the trig-
ger assigned to the "Load parameter set" funcon in 0x2631:040
(P400.40) provides a FALSE-TRUE edge.
4Example: Acvaon via command (immediately)^ 533
2 If the selecon is changed (disable required) The parameter set selected via the funcons "Select parameter set (bit
0)" and "Select parameter set (bit 1)" is acvated if the state of these
selecon bits changes AND the inverter is inhibited, the motor is stop-
ped or an error is acve.
4Example: Acvaon if the selecon is changed (only if the inverter is
disabled)^ 534
3 If the selecon is changed (immediately) The parameter set selected via the funcons "Select parameter set (bit
0)" and "Select parameter set (bit 1)" is acvated immediately if the
state of these selecon bits is changed.
4Example: Acvaon if the selecon is changed (immediately)^ 535
Addional funcons
Parameter change-over
Funcons for parameter change-over